| Plan Review Notes For Permit 23010083 |
| Permit Number |
23010083 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-06-22 15:17:29 | BUILDING REVIEW APPROVED WITH PROVISO (PER ARCHITECT'S | | | REQUEST): | | | (NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO | | | INSPECTIONS TO AVOID CONFLICTS/DELAYS): | | | 1- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE | | | ELEVATOR INSTALLATION UNDER A SEPARATE PERMIT. | | | 2- REVISE ROOF SHEATHING NAIL SPACING SPECS. 4 INCHES | | | O.C. TABLE R803.2.3.1 FBC-RESIDENTIAL. | | | 3- REVISE WOOD FRAMED WALLS SPECS: NEED 2 LAYERS OF | | | WATER RESISTIVE BARRIERS. | | | 4- NEED CARBON MONOXIDE ALARM WITHIN 10 FEET OF BEDROOM | | | #1. | | | 5- CRAWL SPACE VENTS. SHOW COMPLIANCE WITH VENT | | | LOCATION & ACCESS. SEC. R408.2 AND SEC. R408.4 | | | FBC-RESIDENTIAL. | | | 6- SPECIFY SIZE OF HORIZONTAL MULLION FOR WINDOW #9. | | | AND MARK SIZE IN PRODUCT APPROVAL. | | | 7- RESUBMIT CASEMENT WINDOWS, FIXED WINDOWS, WINDOW | | | MULLIONS, SINGLE HUNG WINDOWS AND FRENCH DOORS PRODUCT | | | APPROVALS. THEY WERE REVISED AND WERE NOT APPROVED BY | | | THE ARCHITECT. | | | 8- COORDINATE AND RESUBMIT ALL ROOFING PRODUCT | | | APPROVALS AFTER THIS BUILDING PERMIT IS ISSUED. SOME | | | PRODUCT APPROVALS WERE MISMATCHED, AND SOME WERE NOT | | | APPROVED BY THE ARCHITECT. |
|