| 2023-03-10 12:41:25 | 1ST REVIEW FBC-2020 RES. PLUMBING |
| | PERMIT- 23010083 |
| | 3/10/23 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 13 MAIN HOUSE PLUMBING RISERS: THE RISERS SHOW |
| | IMPROPER VENTING OF THE BATHROOM AND LAUNDRY FIXTURES. |
| | PLEASE CORRECT PER ITEMS A, B & C BELOW. |
| | |
| | A) 1ST FLOOR RISER: THE WASHER FIXTURE DRAIN AND TRAP |
| | REQUIRES AN INDIVIDUAL VENT AND THE DRAIN SHALL CONNECT |
| | DOWNSTREAM OF THE POWDER ROOM WET VENT- SECS. P3106.1 & |
| | P3108.1 FBC RES. |
| | |
| | B) 2ND FLOOR RISER: IMPROPER WET VENTING FOR THE MASTER |
| | BATH AND THE BATH IN THE CENTER OF THE RISER. PLEASE |
| | SEE SEC. P3108.2.1 FBC RES- NOT MORE THAN ONE |
| | WET-VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF |
| | THE DRY-VENTED FIXTURE DRAIN CONNECTION. THE DRAWING |
| | SHOWS THE MASTER BATH TUB AND WC FIXTURE DRAINS UP |
| | STREAM OF THE LAVATORY FIXTURE DRAIN CONNECTION, AND |
| | THE CENTER BATH SHOWER AND WC DRAINS UPSTREAM OF THE |
| | LAVATORY- PLEASE CORRECT. |
| | |
| | C) 2ND FLOOR RISER: WASHING MACHINE DRAIN AND VENT NOT |
| | SHOWN ON THE RISER- SEC. P3101.2.1 FBC RES. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |