| 2023-03-10 07:26:58 | 1ST REVIEW FMC |
| | PERMIT: 23010083 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | COULD NOT COMPLETE A MECHANICAL REVIEW AS NOT ALL OF |
| | THE INFORMATION WAS PROVIDED. |
| | |
| | 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS |
| | INDICATES 4 ZONES. LABEL THESE ZONES ON THE MECHANICAL |
| | DRAWINGS. FBC 107.3.5 |
| | |
| | 2) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS |
| | INDICATES THAT ZONE 4 DOES NOT HAVE A HEATING INPUT OR |
| | OUTPUT. PLEASE EXPLAIN HOW THIS WOULD MEET THE HEATING |
| | REQUIREMENTS OF FRC R303.10 |
| | |
| | 3) PROVIDE AN EQUIPMENT SCHEDULE SHEET FOR ALL OF THE |
| | MECHANICAL SYSTEMS INCLUDING THE BATH EXHAUST FANS. FBC |
| | 107.3.5 |
| | |
| | 4) PROVIDE INFORMATION FOR THE KITCHEN HOOD MOTOR. WHAT |
| | ARE THE CFMS? IF NEEDED SHOW THE MAKEUP AIR FOR THIS |
| | FAN. FRC M1503.4 |
| | |
| | 5) SHOW HOW THE 6 INCH DRYER EXHAUST DUCT SIZE WILL |
| | MEET FRC M1502.4.1 |
| | |
| | 6) PROVIDE THE MECHANICAL DESIGN FOR THE ACCESSORY |
| | STRUCTURE. FBC 1073.5 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |