| 2023-05-15 11:00:53 | 3RD REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23010061 |
| | 5/15/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST AND 2ND REVIEW ARE COPIED BELOW. I HAVE PROVIDED |
| | ADDITIONAL NOTES BELOW EACH COMMENT FOR CLARIFICATION. |
| | PLEASE CORRECT THE PLANS TO AVOID A PENALTY FEE OF FOUR |
| | TIMES THE AMOUNT OF THE PERMIT FEE- SEE FL. STATUTE |
| | 553.80. ALSO AS PREVIOUSLY REQUESTED PROVIDE THE |
| | REQUESTED RESPONSE NARRATIVES FROM THE ARCHITECT AND |
| | ENGINEER ADDRESSING ALL OF THE COMMENTS. |
| | |
| | 1) FAILED. P-100: PLEASE NOTE THAT A SEPARATE PERMIT IS |
| | REQUIRED FOR THE GREASE INTERCEPTOR INSTALLATION- SEC. |
| | 107.2.1 WPB. DUE TO A CHANGE IN PROCESS, THE GREASE |
| | INTERCEPTOR IS REQUIRED TO BE SUBMITTED PRIOR TO THE |
| | MAIN PLUMBING PLAN APPROVAL. YOU CAN SUBMIT AN |
| | APPLICATION TBD (TO BE DETERMINED) IF YOU DO NOT HAVE A |
| | CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT |
| | APPLICATION TO [email protected] . YOU WILL |
| | RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| | MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| | APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT |
| | YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER |
| | YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL |
| | AND I WILL CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | NOTE: THE SEPARATE PERMIT APPLICATION FOR THE GREASE |
| | INTERCEPTOR WAS NOT SUBMITTED. THE PLUMBING PLANS FOR |
| | THE RESTAURANT WILL NOT BE APPROVED WITHOUT THE |
| | APPLICATION. |
| | |
| | |
| | 3) FAILED. P-110 & P-200: THE PLAN SHOWS NUMEROUS |
| | FIXTURES WITH NON-GREASE LADEN WASTEWATER DRAINING INTO |
| | THE GREASE INTERCEPTOR WHICH IS PROHIBITED PER SEC. |
| | 1003.3.1 FBC P. FIXTURES IN VIOLATION ARE THE HAND SINK |
| | (P67), THE ICE MAKERS (P52) (P54) THE ICE BINS (P53) |
| | (P55), AND THE BAR FIXTURES (B3, B6, B7, B9, B12). |
| | |
| | NOTE: NO CORRECTIONS TO THE PLANS WERE MADE. PLEASE |
| | COMPLY WITH THE COMMENT. |
| | |
| | 5) FAILED. P-210: PLEASE PROVIDE A WATER RISER DRAWING- |
| | SEC. 107.3.5.1.3 WPB. THE RISER SHALL SHOW THE PIPE |
| | SIZES (NO SIZES WERE PROVIDED ON THE PLAN), AND |
| | LOCATIONS OF REQUIRED WATER HAMMER ARRESTORS AND SUPPLY |
| | LINE BACKFLOW PREVENTERS FOR APPLIANCES SUCH AS |
| | DISHWASHERS, BEVERAGE AND COFFEE MACHINES, WATER |
| | FILTERS- SEC. 604.9 & 608.3 FBC P. |
| | |
| | NOTE: BACKFLOW PREVENTER LOCATIONS NOT SHOWN ON THE |
| | RISER DRAWING. |
| | |
| | 7) FAILED. P-210: INDICATE HOW TEMPERED WATER WILL BE |
| | DELIVERED FROM THE BATHROOM LAVATORY SINKS- SEC. 419.5 |
| | FBC P. |
| | |
| | NOTE: NO RESPONSE TO THE COMMENT WAS PROVIDED, AND |
| | TEMPERED WATER NOT PROVIDED. |
| | |
| | 8) FAILED. P-210: IT APPEARS THE LENGTHS OF THE HW |
| | SUPPLY PIPES TO THE LAVATORIES HAVE EXCEEDED THEIR |
| | MAXIMUM LENGTHS ALLOWABLE PER TABLE C404.1 FBC EC. |
| | |
| | NOTE: BASED ON TABLE C404.1.THE MAXIMUM LENGTHS OF THE |
| | HW SUPPLY PIPES TO THE LAVATORIES FROM THE HOT WATER |
| | SOURCE IS 2 FT. IN ORDER TO MEET COMPLIANCE THE |
| | RECIRCULATION LINE MUST LOOP DOWN TO EACH OF THE |
| | LAVATORIES AND CONNECT TO THE SUPPLY WITHIN 2 FT. OF |
| | THE FIXTURE. OTHERWISE, A POINT OF USE WATER HEATER |
| | SHALL BE PROVIDED AT EACH LAVATORY. |
| | |
| | 11) FAILED. A-1.3, A-1.4, A-1.5: PLEASE PROVIDE THE |
| | FOLLOWING FBC ACC COMPLIANCE DETAILS FOR THE CUSTOMER |
| | AND EMPLOYEE RESTROOMS: |
| | |
| | A) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR |
| | THE WATER CLOSETS- SEC. 604.3. |
| | NOTE: BASED ON THE DIMENSIONS SHOWN ON SHEETS A-1.3 & |
| | A-1.4 IT APPEARS THE CLEAR FLOOR SPACES FOR THE WATER |
| | CLOSETS WILL BE OVERLAPPING THE LAVATORIES WHICH IS NOT |
| | PERMITTED PER SEC. 604.3.2 FBC ACC. |
| | |
| | I) FAILED. KNEE AND TOE CLEARANCES FOR THE LAVATORIES- |
| | SEC. 606.2. |
| | NOTE: NO DETAIL PROVIDED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |