| 2023-05-15 12:03:10 | 3RD REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 23010061 |
| | 5/15/23 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST AND 2ND REVIEW ARE COPIED BELOW. I HAVE PROVIDED |
| | ADDITIONAL NOTES BELOW EACH COMMENT FOR CLARIFICATION. |
| | PLEASE CORRECT THE PLANS TO AVOID A PENALTY FEE OF FOUR |
| | TIMES THE AMOUNT OF THE PERMIT FEE- SEE FL. STATUTE |
| | 553.80. ALSO AS PREVIOUSLY REQUESTED PROVIDE THE |
| | REQUESTED RESPONSE NARRATIVE FROM THE ENGINEER |
| | ADDRESSING ALL OF THE COMMENTS. |
| | |
| | |
| | 1) FAILED.SHEET P-320 GAS RISER CORRECTIONS: |
| | A) BASED ON THE LONGEST LENGTH METHOD FOR GAS PIPE |
| | SIZING, THE 1/2- INCH PIPE TO THE GWH IS UNDERSIZED PER |
| | TABLE 402.4(2) FBC FG. THE MINIMUM SIZE REQUIRED IS |
| | 1-1/4-INCH. |
| | B) PLEASE LABEL THE SIZES OF THE INDIVIDUAL SUPPLY |
| | PIPES TO THE COOKING APPLIANCES- SEC. 402.3 FBC FG. |
| | C) PLEASE CLARIFY THE PURPOSE OF THE GAS PIPING |
| | MANIFOLDS FOR EACH COOKING LINE- SEC. 107.2.1 WPB. |
| | |
| | 2) FAILED. SHEETS P-210 & M-300: THE COMBUSTION AIR |
| | CALCULATIONS ARE NOT IN COMPLIANCE WITH SEC. 304.9.3 |
| | COMBINED COMBUSTION AIR AND VENTILATION AIR SYSTEM. |
| | WHERE COMBUSTION AIR IS PROVIDED BY THE BUILDING'S |
| | MECHANICAL VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE |
| | THE SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE |
| | REQUIRED VENTILATION AIR. |
| | KSF IS SUPPLYING MAKEUP AIR FOR THE HOOD EXHAUST, AND |
| | FCU-3 IS SUPPLYING OA FOR THE KITCHEN OCCUPANTS. |
| | ADDITIONAL AIR IS REQUIRED FOR COMBUSTION AIR. |
| | |
| | 3) FAILED. P-210: PLEASE SHOW THE GWH INTAKE AND |
| | EXHAUST PIPE TERMINATION LOCATIONS ON THE PLAN- SEC. |
| | AND TABLE 503.8 FBC FG. |
| | |
| | 4) FAILED.P-210 & M-300: PLEASE SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE WOOD/COAL/GAS OVEN TO VERIFY THE |
| | APPLIANCE MEETS CURRENT LISTING STANDARDS AND PROVIDES |
| | RECOMMENDATIONS FOR THE EXHAUST SYSTEM- SECS. 305.1 & |
| | 623.1 FBC FG. |
| | |
| | A) PROVIDE AN EXHAUST VENTING DIAGRAM SHOWING THE TYPE |
| | AND SIZE OF VENT, VENT RUN LENGTH, AND TERMINATION |
| | LOCATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |