Plan Review Notes
Plan Review Notes For Permit 23010061
Permit Number 23010061
Review Stop P
Sequence Number 2
Notes
Date Text
2023-04-05 15:28:192ND REVIEW FBC-2020 PLUMBING
 PERMIT- 23010061
 4/5/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE COPIED BELOW. I HAVE PROVIDED ADDITIONAL
 NOTES BELOW EACH COMMENT FOR CLARIFICATION.
  
 1) P-100: PLEASE NOTE THAT A SEPARATE PERMIT IS
 REQUIRED FOR THE GREASE INTERCEPTOR INSTALLATION- SEC.
 107.2.1 WPB. DUE TO A CHANGE IN PROCESS, THE GREASE
 INTERCEPTOR IS REQUIRED TO BE SUBMITTED PRIOR TO THE
 MAIN PLUMBING PLAN APPROVAL. YOU CAN SUBMIT AN
 APPLICATION TBD (TO BE DETERMINED) IF YOU DO NOT HAVE A
 CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL
 AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 NOTE: THE SEPARATE PERMIT APPLICATION FOR THE GREASE
 INTERCEPTOR WAS NOT SUBMITTED. THE PLUMBING PLANS FOR
 THE RESTAURANT WILL NOT BE APPROVED WITHOUT THE
 APPLICATION.
  
 2) SHEET LS-1 OR P-100: PROVIDE PLUMBING FIXTURES
 CALCULATIONS IN COMPLIANCE WITH TABLE 403.1 FBC P.
 PROVIDE A SCHEDULE THAT SHOWS THE REQUIRED AND PROVIDED
 NUMBER OF FIXTURES FOR THE OCCUPANCY.
  
 NOTE: RESPONSE NOT PROVIDED. IT APPEARS THE REQUIRED
 NUMBER OF WATER CLOSETS AND LAVATORIES HAVE BEEN
 PROVIDED HOWEVER DRINKING FOUNTAINS ARE REQUIRED UNLESS
 WATER WILL BE SERVED FREE OF CHARGE IN ACCORDANCE WITH
 SEC. 410.4.
  
 3) P-110 & P-200: THE PLAN SHOWS NUMEROUS FIXTURES WITH
 NON-GREASE LADEN WASTEWATER DRAINING INTO THE GREASE
 INTERCEPTOR WHICH IS PROHIBITED PER SEC. 1003.3.1 FBC
 P. FIXTURES IN VIOLATION ARE THE HAND SINK (P67), THE
 ICE MAKERS (P52) (P54) THE ICE BINS (P53) (P55), AND
 THE BAR FIXTURES (B3, B6, B7, B9, B12).
  
 NOTE: NO CORRECTIONS TO THE PLANS WERE MADE. PLEASE
 COMPLY WITH THE COMMENT.
  
 5) P-210: PLEASE PROVIDE A WATER RISER DRAWING- SEC.
 107.3.5.1.3 WPB. THE RISER SHALL SHOW THE PIPE SIZES
 (NO SIZES WERE PROVIDED ON THE PLAN), AND LOCATIONS OF
 REQUIRED WATER HAMMER ARRESTORS AND SUPPLY LINE
 BACKFLOW PREVENTERS FOR APPLIANCES SUCH AS DISHWASHERS,
 BEVERAGE AND COFFEE MACHINES, WATER FILTERS- SEC. 604.9
 & 608.3 FBC P.
  
 NOTE: BACKFLOW PREVENTER LOCATIONS NOT SHOWN ON THE
 RISER DRAWING.
  
 7) P-210: INDICATE HOW TEMPERED WATER WILL BE DELIVERED
 FROM THE BATHROOM LAVATORY SINKS- SEC. 419.5 FBC P.
  
 NOTE: NO RESPONSE TO THE COMMENT WAS PROVIDED, AND
 TEMPERED WATER NOT PROVIDED.
  
 8) P-210: IT APPEARS THE LENGTHS OF THE HW SUPPLY PIPES
 TO THE LAVATORIES HAVE EXCEEDED THEIR MAXIMUM LENGTHS
 ALLOWABLE PER TABLE C404.1 FBC EC.
  
 NOTE: BASED ON TABLE C404.1.THE MAXIMUM LENGTHS OF THE
 HW SUPPLY PIPES TO THE LAVATORIES FROM THE HOT WATER
 SOURCE IS 2 FT. IN ORDER TO MEET COMPLIANCE THE
 RECIRCULATION LINE MUST LOOP DOWN TO EACH OF THE
 LAVATORIES AND CONNECT TO THE SUPPLY WITHIN 2 FT. OF
 THE FIXTURE. OTHERWISE, A POINT OF USE WATER HEATER
 SHALL BE PROVIDED AT EACH LAVATORY.
  
 11) A-1.3, A-1.4, A-1.5: PLEASE PROVIDE THE FOLLOWING
 FBC ACC COMPLIANCE DETAILS FOR THE CUSTOMER AND
 EMPLOYEE RESTROOMS:
  
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SEC. 604.3.
 NOTE: BASED ON THE DIMENSIONS SHOWN ON SHEETS A-1.3 &
 A-1.4 IT APPEARS THE CLEAR FLOOR SPACES FOR THE WATER
 CLOSETS WILL BE OVERLAPPING THE LAVATORIES WHICH IS NOT
 PERMITTED PER SEC. 604.3.2 FBC ACC.
  
 I) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2.
 NOTE: NO DETAIL PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  