Plan Review Notes For Permit 23010061
Permit Number 23010061
Review Stop M
Sequence Number 2
Notes
Date Text
2023-04-07 09:47:022ND REVIEW FMC
 PERMIT: 23010061
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) SHEET M-300: PLEASE PROVIDE THE OUTDOOR AIR
 CALCULATIONS BASED ON THE OCCUPANCY CLASSIFICATION AND
 OCCUPANT DENSITY FROM FMC TABLE 403.3.1.1 AND NOT THE
 ARCHITECTS EGRESS COUNTS.
  
 2) SHEET M-300: PROVIDE THE AIR BALANCE REPORT BASED ON
 THE CORRECTED OUTDOOR AIR CALCULATIONS. THE AIR BALANCE
 DESIGN CAN ONLY TRANSFER AIR FROM OTHER SPACES THAT IS
 ABOVE THE REQUIRED AIR FOR THAT SPACE. PLEASE SHOW THE
 AMOUNT OF AIR THAT WILL BE TRANSFERRED FROM THE DINING
 AREAS INTO THE KITCHEN IN THE AIR BALANCE REPORT. THIS
 AIR SHOULD ONLY BE THAT WHICH IS ABOVE THE AMOUNT OF
 OUTDOOR AIR REQUIRED FOR THE OCCUPANTS AND THE SPACE
 FOR THE DINING ROOMS. FMC 508.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  