| 2023-04-07 09:47:02 | 2ND REVIEW FMC |
| | PERMIT: 23010061 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | |
| | 1) SHEET M-300: PLEASE PROVIDE THE OUTDOOR AIR |
| | CALCULATIONS BASED ON THE OCCUPANCY CLASSIFICATION AND |
| | OCCUPANT DENSITY FROM FMC TABLE 403.3.1.1 AND NOT THE |
| | ARCHITECTS EGRESS COUNTS. |
| | |
| | 2) SHEET M-300: PROVIDE THE AIR BALANCE REPORT BASED ON |
| | THE CORRECTED OUTDOOR AIR CALCULATIONS. THE AIR BALANCE |
| | DESIGN CAN ONLY TRANSFER AIR FROM OTHER SPACES THAT IS |
| | ABOVE THE REQUIRED AIR FOR THAT SPACE. PLEASE SHOW THE |
| | AMOUNT OF AIR THAT WILL BE TRANSFERRED FROM THE DINING |
| | AREAS INTO THE KITCHEN IN THE AIR BALANCE REPORT. THIS |
| | AIR SHOULD ONLY BE THAT WHICH IS ABOVE THE AMOUNT OF |
| | OUTDOOR AIR REQUIRED FOR THE OCCUPANTS AND THE SPACE |
| | FOR THE DINING ROOMS. FMC 508.2 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |