| 2023-04-05 16:35:29 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 23010061 |
| | 4/5/23 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P-320 GAS RISER CORRECTIONS: |
| | A) BASED ON THE LONGEST LENGTH METHOD FOR GAS PIPE |
| | SIZING, THE 1/2- INCH PIPE TO THE GWH IS UNDERSIZED PER |
| | TABLE 402.4(2) FBC FG. THE MINIMUM SIZE REQUIRED IS |
| | 1-1/4-INCH. |
| | B) PLEASE LABEL THE SIZES OF THE INDIVIDUAL SUPPLY |
| | PIPES TO THE COOKING APPLIANCES- SEC. 402.3 FBC FG. |
| | C) PLEASE CLARIFY THE PURPOSE OF THE GAS PIPING |
| | MANIFOLDS FOR EACH COOKING LINE- SEC. 107.2.1 WPB. |
| | |
| | 2) SHEETS P-210 & M-300: THE COMBUSTION AIR |
| | CALCULATIONS ARE NOT IN COMPLIANCE WITH SEC. 304.9.3 |
| | COMBINED COMBUSTION AIR AND VENTILATION AIR SYSTEM. |
| | WHERE COMBUSTION AIR IS PROVIDED BY THE BUILDING'S |
| | MECHANICAL VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE |
| | THE SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE |
| | REQUIRED VENTILATION AIR. |
| | KSF IS SUPPLYING MAKEUP AIR FOR THE HOOD EXHAUST, AND |
| | FCU-3 IS SUPPLYING OA FOR THE KITCHEN OCCUPANTS. |
| | ADDITIONAL AIR IS REQUIRED FOR COMBUSTION AIR. |
| | |
| | 3) P-210: PLEASE SHOW THE GWH INTAKE AND EXHAUST PIPE |
| | TERMINATION LOCATIONS ON THE PLAN- SEC. AND TABLE 503.8 |
| | FBC FG. |
| | |
| | 4) P-210 & M-300: PLEASE SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE WOOD/COAL/GAS OVEN TO VERIFY THE |
| | APPLIANCE MEETS CURRENT LISTING STANDARDS AND PROVIDE |
| | RECOMMENDATIONS FOR THE EXHAUST SYSTEM- SECS. 305.1 & |
| | 623.1 FBC FG. |
| | |
| | A) PROVIDE AN EXHAUST VENTING DIAGRAM SHOWING THE TYOE |
| | AND SIZE OF VENT, VNT RUN LENGTH, AND TERMINATION |
| | LOCATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |