| 2023-01-06 12:21:55 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23010061 |
| | 1/6/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) P-100: PLEASE NOTE THAT A SEPARATE PERMIT IS |
| | REQUIRED FOR THE GREASE INTERCEPTOR INSTALLATION- SEC. |
| | 107.2.1 WPB. DUE TO A CHANGE IN PROCESS, THE GREASE |
| | INTERCEPTOR IS REQUIRED TO BE SUBMITTED PRIOR TO THE |
| | MAIN PLUMBING PLAN APPROVAL. YOU CAN SUBMIT AN |
| | APPLICATION TBD (TO BE DETERMINED) IF YOU DO NOT HAVE A |
| | CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT |
| | APPLICATION TO [email protected] . YOU WILL |
| | RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| | MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| | APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT |
| | YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER |
| | YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL |
| | AND I WILL CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | 2) SHEET LS-1 OR P-100: PROVIDE PLUMBING FIXTURES |
| | CALCULATIONS IN COMPLIANCE WITH TABLE 403.1 FBC P. |
| | PROVIDE A SCHEDULE THAT SHOWS THE REQUIRED AND PROVIDED |
| | NUMBER OF FIXTURES FOR THE OCCUPANCY. |
| | |
| | 3) P-110 & P-200: THE PLAN SHOWS NUMEROUS FIXTURES WITH |
| | NON-GREASE LADEN WASTEWATER DRAINING INTO THE GREASE |
| | INTERCEPTOR WHICH IS PROHIBITED PER SEC. 1003.3.1 FBC |
| | P. FIXTURES IN VIOLATION ARE THE HAND SINK (P67), THE |
| | ICE MAKERS (P52) (P54) THE ICE BINS (P53) (P55), AND |
| | THE BAR FIXTURES (B3, B6, B7, B9, B12). |
| | |
| | 4) P-110 & P-200: PLEASE ADD THE FLOOR DRAINS TO THE |
| | SCHEDULE AND INDICATE HOW TRAP SEAL PROTECTION WILL BE |
| | PROVIDED- SEC. 1002.4.1.1 FBC P. |
| | |
| | 5) P-210: PLEASE PROVIDE A WATER RISER DRAWING- SEC. |
| | 107.3.5.1.3 WPB. THE RISER SHALL SHOW THE PIPE SIZES |
| | (NO SIZES WERE PROVIDED ON THE PLAN), AND LOCATIONS OF |
| | REQUIRED WATER HAMMER ARRESTORS AND SUPPLY LINE |
| | BACKFLOW PREVENTERS FOR APPLIANCES SUCH AS DISHWASHERS, |
| | BEVERAGE AND COFFEE MACHINES, WATER FILTERS- SEC. 604.9 |
| | & 608.3 FBC P. |
| | |
| | 6) P-200: PROVIDE PIPE SIZES (DIAMETERS) ON THE PLAN OR |
| | THE NEW RISER- SEC. 604.3 FBC P. |
| | |
| | 7) P-210: INDICATE HOW TEMPERED WATER WILL BE DELIVERED |
| | FROM THE BATHROOM LAVATORY SINKS- SEC. 419.5 FBC P. |
| | |
| | 8) P-210: IT APPEARS THE LENGTHS OF THE HW SUPPLY PIPES |
| | TO THE LAVATORIES HAVE EXCEEDED THEIR MAXIMUM LENGTHS |
| | ALLOWABLE PER TABLE C404.1 FBC EC. |
| | |
| | 9) P-400: PLEASE CORRECT THE NOTE INCLUDING RELIEF |
| | VALVE DISCHARGE PIPE TO OUTSIDE OF THE BUILDING. BASED |
| | ON THE WH LOCATION ON THE PLAN IT WOULD NOT BE |
| | POSSIBLE- SEC. 504.6 FBC P. |
| | |
| | 10) P-200 & P-500: GREASE INTERCEPTOR- PROVIDE THE |
| | FOLLOWING DETAILS AND NOTES PER SEC.1003.3.5 FBC P. |
| | PLEASE NOTE SHEET P-510 WHICH IS REFERENCED ON THE |
| | SAINTARY ISOMETRIC BY THE GREASE INTERCEPTOR WAS NOT |
| | UPLOADED FOR REVIEW. |
| | A) PROVIDE SIZING CALCULATIONS. |
| | B) PROIVDE AN ENLARGED PIPING INSTALLATION DETAIL- SEC. |
| | 1003.3.5 FBC P. TYPICAL MANUFACTURER'S GUIDELINES |
| | REQUIRE CLEANOUTS ON BOTH THE INLET AND OUTLET PIPES. |
| | THE WPB UTILITIES DEPARTMENT REQUIRES A CLEANOUT ON THE |
| | OIUTLET PIPE FOR SAMPLING. |
| | |
| | 11) A-1.3, A-1.4, A-1.5: PLEASE PROVIDE THE FOLLOWING |
| | FBC ACC COMPLIANCE DETAILS FOR THE CUSTOMER AND |
| | EMPLOYEE RESTROOMS: |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SEC. 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORIES- SEC. 606.2. |
| | C) TURNING SPACE DIAMETERS- SEC. 304.3. PLEASE INCLUDE |
| | THE EMPLOYEE RESTROOM. |
| | D) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SEC. 604.4. |
| | E) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE |
| | FROM THE FINISHED FLOOR- SEC. 606.3. |
| | F) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SEC. 603.3 |
| | G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. |
| | H) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE |
| | 604.7. |
| | I) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC. |
| | 606.2 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |