| 2023-01-06 13:14:57 | 1ST REVIEW FMC |
| | PERMIT: 23010061 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | KITCHEN HOODS: |
| | 1) KITCHEN HOODS AND EQUIPMENT MUST BE SUBMITTED |
| | SEPARATELY FOR REVIEW AND PERMITTING. ADD A NOTE TO THE |
| | MECHANICAL DRAWINGS STATING THAT THE KITCHEN HOODS AND |
| | GREASE DUCTS FOR THIS PROJECT WILL REQUIRE A SEPARATE |
| | PERMIT APPLICATION AND DOCUMENT SUBMITTAL AS THEY WILL |
| | NOT BE REVIEWED UNDER THIS PERMIT. |
| | |
| | REFRIGERATION: |
| | 2) REFRIGERATION PLAN HAS BEEN LOCKED AND WILL NOT BE |
| | PRINTED WITH THIS VERSION. REFRIGERATION EQUIPMENT MUST |
| | BE SUBMITTED SEPARATELY FOR REVIEW AND PERMITTING. ADD |
| | A NOTE TO THE MECHANICAL DRAWINGS STATING THAT THE |
| | REFRIGERATION FOR THIS PROJECT WILL REQUIRE A SEPARATE |
| | PERMIT APPLICATION AND DOCUMENT SUBMITTAL AS THEY WILL |
| | NOT BE REVIEWED UNDER THIS PERMIT. |
| | |
| | 3) SHEET M-200: SHOW THAT THE OUTDOOR AIR TERMINATION |
| | LOCATION WILL MEET THE REQUIREMENTS OF THE FMC 401.4. |
| | |
| | 4) SHEET M-200: PROVIDE ON THE DRAWINGS, THE LOCATION |
| | OF THE OUTDOOR AIR TERMINATION FOR FCU-2 AND FCU-3 AND |
| | SHOW THAT THE TERMINATION LOCATION COMPLIES WITH FMC |
| | 401.4 |
| | |
| | 5) SHEET M-300: PROVIDE OUTDOOR AIR CALCULATIONS BASED |
| | ON THE OCCUPANT DENSITY OF TABLE 403.3.1.1. FMC |
| | 403.3.1.1 |
| | |
| | 6) PROVIDE MECHANICAL EQUIPMENT SIZING CALCULATIONS |
| | BASED ON THE OCCUPANCY CLASSIFICATION AND OCCUPANT |
| | DENSITY FOR EACH FCU ACCORDING TO THE NUMBER OF PEOPLE |
| | FROM FBC TABLE 403.3.1.1 |
| | |
| | 7) SHEET M-200: THE BATH EXHAUST FANS ARE ALL |
| | EXHAUSTING INTO 1 12 X 10 INCH DUCT. SHOW THIS ENTIRE |
| | DUCT, LENGTH AND TERMINATION LOCATION. SHOW THAT THIS |
| | DUCT WILL MAINTAIN THE VELOCITY REQUIRED TO EXHAUST THE |
| | BATHROOMS. FMC 403.3.2.3 |
| | |
| | 8) SHOW THE REQUIRED DUCT DETECTORS IN THE SUPPLY DUCTS |
| | OF THE FCU???S. FMC 606.2 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |