Plan Review Notes
Plan Review Notes For Permit 23010061
Permit Number 23010061
Review Stop M
Sequence Number 1
Notes
Date Text
2023-01-06 13:14:571ST REVIEW FMC
 PERMIT: 23010061
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 KITCHEN HOODS:
 1) KITCHEN HOODS AND EQUIPMENT MUST BE SUBMITTED
 SEPARATELY FOR REVIEW AND PERMITTING. ADD A NOTE TO THE
 MECHANICAL DRAWINGS STATING THAT THE KITCHEN HOODS AND
 GREASE DUCTS FOR THIS PROJECT WILL REQUIRE A SEPARATE
 PERMIT APPLICATION AND DOCUMENT SUBMITTAL AS THEY WILL
 NOT BE REVIEWED UNDER THIS PERMIT.
  
 REFRIGERATION:
 2) REFRIGERATION PLAN HAS BEEN LOCKED AND WILL NOT BE
 PRINTED WITH THIS VERSION. REFRIGERATION EQUIPMENT MUST
 BE SUBMITTED SEPARATELY FOR REVIEW AND PERMITTING. ADD
 A NOTE TO THE MECHANICAL DRAWINGS STATING THAT THE
 REFRIGERATION FOR THIS PROJECT WILL REQUIRE A SEPARATE
 PERMIT APPLICATION AND DOCUMENT SUBMITTAL AS THEY WILL
 NOT BE REVIEWED UNDER THIS PERMIT.
  
 3) SHEET M-200: SHOW THAT THE OUTDOOR AIR TERMINATION
 LOCATION WILL MEET THE REQUIREMENTS OF THE FMC 401.4.
  
 4) SHEET M-200: PROVIDE ON THE DRAWINGS, THE LOCATION
 OF THE OUTDOOR AIR TERMINATION FOR FCU-2 AND FCU-3 AND
 SHOW THAT THE TERMINATION LOCATION COMPLIES WITH FMC
 401.4
  
 5) SHEET M-300: PROVIDE OUTDOOR AIR CALCULATIONS BASED
 ON THE OCCUPANT DENSITY OF TABLE 403.3.1.1. FMC
 403.3.1.1
  
 6) PROVIDE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 BASED ON THE OCCUPANCY CLASSIFICATION AND OCCUPANT
 DENSITY FOR EACH FCU ACCORDING TO THE NUMBER OF PEOPLE
 FROM FBC TABLE 403.3.1.1
  
 7) SHEET M-200: THE BATH EXHAUST FANS ARE ALL
 EXHAUSTING INTO 1 12 X 10 INCH DUCT. SHOW THIS ENTIRE
 DUCT, LENGTH AND TERMINATION LOCATION. SHOW THAT THIS
 DUCT WILL MAINTAIN THE VELOCITY REQUIRED TO EXHAUST THE
 BATHROOMS. FMC 403.3.2.3
  
 8) SHOW THE REQUIRED DUCT DETECTORS IN THE SUPPLY DUCTS
 OF THE FCU???S. FMC 606.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  