2023-01-06 13:13:151ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 23010061
 1/3/2023
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-210: COMPLETE GAS PLANS WERE NOT UPLOADED
 FOR REVIEW BUT ARE REQUIRED PER SEC. 107.3.5.1.5 WPB.
 PLEASE PROVIDE THE FOLLOWING COMPLIANCE DRAWINGS AND
 DETAILS PER FBC FG.
 A) GAS RISER- SEC. 402.1.
  
 B) COMBUSTION AIR CALCULATIONS FOR THE COOKING
 APPLIANCES- SECS. 304.1.
  
 C) WATER HEATER COMBUSTION AIR AND VENTING- SECS. 503.1
 & 624.1. THE PLAN SHOWS A DIRECT VENT SYSTEM PER
 MANUFACTURER???S RECOMMENDATION. PLEASE PROVIDE A
 DIAGRAM PER THE SPECS THAT SHOWS THE TOTAL RUN LENGTHS
 OF THE 4-INCH INTAKE AND EXHAUST PIPES AND TERMINATION
 LOCATIONS. PLEASE INCLUDE THE TYPE OF INTAKE AND
 EXHAUST PIPE MATERIAL AS RECOMMENDED BY THE
 MANUFACTURER.
  
 2) THE GAS RISER DRAWING SHALL INCLUDE THE FOLLOWING
 INFORMATION:
 A) DELIVERY PRESSURE AT THE METER.
 B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 C) TYPES AND SIZES OF PIPING.
 D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 F) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND
 REGULATOR VENT PIPING DETAILS (IF APPLICABLE).
 G) OUTLET PRESSURES AT REGULATORS.
 H) LOCATIONS AND TYPES OF PIPE SLEEVES.
 I) PIPE SIZING TABLES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.