Plan Review Notes
Plan Review Notes For Permit 23010061
Permit Number 23010061
Review Stop B
Sequence Number 1
Notes
Date Text
2023-01-18 11:36:25WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23010061
 ADD: 700 S ROSEMARY AVE # 124
 CONT: JONATHAN ANDREW CONSTRUCTION INC.
 TEL: 305-661-9500
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JAN. 18TH/ 2023
 ACTION: DENIED
  
 1) SHEET 029 LS-1 THE LIFE SAFETY PLAN. THE LIFE SAFETY
 PLAN INDICATES THERE ARE 5 EXITS. EXITS 2, 4 & 5 MEET
 THE REQUIREMENTS FOR EXITS, A MEANS OF EGRESS. PLEASE
 REVIEW IN THE 2020 FBC-BUILDING CODE 1010.1.2 EGRESS
 DOORS SHALL BE OF THE PIVOTED OR SIDE HINGED SWINGING
 TYPE, ALSO SEE EXCEPTIONS. EXIT # 4 IS THE POWER
 SLIDING GLASS DOORS, THIS TYPE OF DOOR WILL ALSO NEED
 TO COMPLY WITH 1010.1.4.3. EXITS 1 & 3 ACCORDION
 HORIZONTAL DOORS DOES MEET THE INTENT OF SECTION
 1010.1.4.3. EXIT 2 & 4 MEET THE OCCUPANT LOADS STATED.
 EXITS 2 & 4 ALSO MEET THE ?? THE DIAGONAL DISTANCE
 APART FOR THE ROOM SERVED.
  
 2A) SHEET 029 LS-1 THE LIFE SAFETY PLAN & SHEET 001 A-1
 PARTITION PLAN SHOW A PRIVATE DINING ROOM, ROOMS ARE
 NOT IDENTIFIED WITH ROOM NUMBERS. THE DINING ROOM HAS
 14 SEATS AROUND THE TABLE AND ENTRY THROUGH DOOR # 07
 HIDDEN TOP AND BOTTOM TRACKS. PLEASE REVIEW THE 2020
 FBC-BUILDING CODE1010.1.2 EXCEPTION # 9 MANUALLY
 OPERATED HORIZONTAL SLIDING DOOR ARE PERMITTED IN A
 MEANS OF EGRESS FROM SPACES WITH AN OCCUPANT LOAD OF 10
 OR LESS.
  
 2B) SHEET 029 LS-1 THE LIFE SAFETY PLAN & SHEET 001 A-1
 PARTITION PLAN SHOW A PRIVATE DINING ROOMS WITH DOOR
 OPENINGS 7 & 8. THE DOOR SCHEDULE SHEET 005 A1.2 LIST
 THESE DOOR TYPES AS DOOR TYPE 3 SLIDING DOOR ASSEMBLY
 HIDDEN TOP AND BOTTOM TRACK. PLEASE SHOW COMPLIANCE
 WITH THE 2020 FBC-ACCESSIBILITY CODE SECTION 302.2.
 OPENINGS IN THE FLOOR. THIS COMMENT HOLDS FOR ALL DOORS
 WITH BOTTOM TRACKS.
  
 3A) SHEET 029 LS-1 THE LIFE SAFETY PLAN & SHEET 001 A-1
 PARTITION PLAN SHOW A PRIVATE DINING ROOM, ROOMS ARE
 NOT IDENTIFIED WITH ROOM NUMBERS. THE PRIVATE DINING
 ROOM IN FRONT OF THE JUST ADDRESSED ABOVE HAS
 APPROXIMATELY 22 SEATS WITH TABLES AND ENTRY THROUGH
 DOOR # 08 IT APPEARS BARN STYLE DOORS. DOOR STYLE # 3
 HIDDEN TOP AND BOTTOM TRACKS. PLEASE REVIEW THE 2020
 FBC-BUILDING CODE1010.1.2 EXCEPTION # 9 MANUALLY
 OPERATED HORIZONTAL SLIDING DOOR ARE PERMITTED IN A
 MEANS OF EGRESS FROM SPACES WITH AN OCCUPANT LOAD OF 10
 OR LESS.
  
 3B) THERE APPEARS TO BE ANOTHER SET OF DOORS INTO THIS
 SPACE, THIS OPENING IS NOT IDENTIFIED WITH A DOOR
 IDENTIFICATION TAG, BUT THE PLAN SHOWS A PAIR OF SWING
 DOORS. AS SHOWN THE DOORS DO NOT TOTALLY ENCLOSE THIS
 DINING ROOM. 2020 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 4) THERE IS A THIRD PRIVATE DINING ROOM ACROSS THE MAIN
 DINING ROOM, AGAIN ROOMS DO NOT HAVE IDENTIFICATION
 TAGS, DOOR # 9 DOOR STYLE 3 HIDDEN TOP AND BOTTOM
 TRACKS. PLEASE REVIEW THE 2020 FBC-BUILDING
 CODE1010.1.2 EXCEPTION # 9 MANUALLY OPERATED HORIZONTAL
 SLIDING DOOR ARE PERMITTED IN A MEANS OF EGRESS FROM
 SPACES WITH AN OCCUPANT LOAD OF 10 OR LESS.
  
 5) SHEET 029 LS-1 THE LIFE SAFETY PLAN SHOWS THE
 ACCESSIBLE WHEELCHAIR LOCATIONS BUT NOT WITH THE
 REQUIRED CLEAR FLOOR SPACE. 2020 FBC-ACCESSIBILITY CODE
 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 SHALL BE PROVIDED. KNEE AND TOE CLEARANCE COMPLYING
 WITH 306 SHALL BE PROVIDED.
  
 6A) SHEET 001 A-1 SHOWS DETAIL S/A-1.1, THIS IS THE
 DROPPED SECTION OF THE BAR FOR ACCESSIBILITY. THE
 DETAIL LACKS SHOWING CLEAR FLOOR OR GROUND SPACE
 SECTION 902.2 OF THE 2020 FBC-ACCESSIBILITY CODE. A
 CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 6B) BAR DETAILS WILL NEED TO SHOW COMPLIANCE WITH THE
 2020 FBC-ACCESSIBILITY CODE SECTIONS:
 306.2 TOE CLEARANCE306.2.2 MAXIMUM DEPTH 306.2.3
 MINIMUM DEPTH 306.2.4 & 306.2.5 AND
 306.3 KNEE CLEARANCE. 306.3.1-306.3.5.
  
 7A) SHEET 029 LIFE SAFETY PLAN SHOWS ACCESSIBLE SEATING
 JUST TO THE RIGHT OF EXIT # 4 ON THE EXTERIOR OF THE
 BUILDING. SHEET 001 A-1 THE PARTITION PLAN SHOWS A
 DETAIL FOR THIS AREA, DETAIL B/A-1.1. THE DETAIL
 INDICATES ON THE EXTERIOR SIDE THE HEIGHT OF THE
 COUNTERTOP IS 42 INCHES IN HEIGHT. THIS HEIGHT DOES NOT
 COMPLY WITH 902.3 HEIGHT. THE TOPS OF DINING SURFACES
 AND WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 7B) FIXED WALL TYPE COUNTERTOP DETAILS WILL NEED TO
 SHOW COMPLIANCE WITH THE 2020 FBC-ACCESSIBILITY CODE
 SECTIONS:
 306.2 TOE CLEARANCE306.2.2 MAXIMUM DEPTH 306.2.3
 MINIMUM DEPTH 306.2.4 & 306.2.5 AND
 306.3 KNEE CLEARANCE. 306.3.1-306.3.5.
  
 8) COMPONENTS & CLADDING. PLEASE SUBMIT THE COMPONENTS
 AND CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 9) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 10) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 11) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE
 OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER???S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 12) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 13) THE ARCHITECTURAL & STRUCTURAL SHEETS SHOW WELDED
 STEEL CONNECTIONS. WELDED OR BOLTED CONNECTIONS. THIS
 BUILDING CONTAINS EITHER BOLTED AND OR WELDED
 CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR RICHARD
 BRUNELLE AT 561-805-6670.
  
 14A) SHEET 006 A-1.2 DETAIL A SHOWS THE USE OF A NEW
 FOLDING DOOR, CROWN DOOR OR EQUAL. 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1. DRAWINGS & SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC TO THE TECHNICAL CODES
 "CODE SECTIONS SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS
 A SUBSTITUTE FOR SPECIFIC INFORMATION".
  
 14B) PLEASE PROVIDE DOCUMENTATION WHERE THE NEW FOLDING
 DOOR MEETS THE REQUIREMENTS FOR SLOPED GLAZING IN
 ACCORDANCE WITH 2405.2 OF THE 2020 FBC-BUILDING CODE.
  
 15) SHEET 028 G-1 NOTES AND FINISHES. WATER CLOSET GRAB
 BARS. THE REAR GRAB BAR HEIGHT IS GIVEN 32-36 INCHES
 FROM CENTERLINE FROM FINISH FLOOR. SIDE WALL GRAB BAR
 33-36 INCHES CENTERLINE. 2020 FBC-ACCESSIBILITY CODE
 SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE.
  
 16A) I???VE LOCATED THE RESTROOM ELEVATION PLANS A-1.3-
 A-1.5. I SEE WALL TAGS FOR ROOM FINISHES BUT I DO NOT
 FIND THE KEY OR SCHEDULE TO IDENTIFY WALL AND FLOOR
 FINISHES. 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS
 COMMENT IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION ON 06/2020. IN BATHROOMS, RESTROOMS &
 SERVICE SINK AREAS EPOXY PAINT IS NO LONGER CONSIDERED
 A SMOOTH HARD, NON-ABSORBENT SURFACE.
  
 16B) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 17) SHEET 056 S1.00 STATEMENT ON FLOOR PLAN. FOUNDATION
 DESIGN FOR CANOPY STRUCTURE PENDING REACTIONS FROM
 SPECIALTY ENGINEER & COORDINATE WITH UNDERGROUND
 UTILITIES. NO INFORMATION HAS BEEN PROVIDED. CANOPY
 WILL BE UNDER SEPARATE PERMIT. 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 18) SHEET 057 S1.01 THE SECOND FLOOR FRAMING PLAN FLOOR
 PENETRATIONS & 060 S2.01 DETAILS. STATEMENT ON PLANS.
 SEE MECHANICAL DRAWINGS FOR THE EXACT SHAFT SIZE AND
 LOCATION. PLEASE PROVIDE LOCATION. AND SIZE BUT ALSO
 THE MATERIAL THE PROPOSED SHAFTS ARE GOING TO BE MADE
 OF. 2020 FBC-BUILDING SECTIONS:
 713.2 CONSTRUCTION
 713.3.MATERIAL
 713.4 FIRE-RESISTANCE RATING
 713.5 CONTINUITY
  
 19) THE STRUCTURAL SHEETS HAVE NO DETAILS FOR ROOF TOP
 CURB CONNECTIONS TO THE ROOF FRAMING NOR THE ROOF TOP
 EXHAUST FANS TO THE CURB.
 2020 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.FBC-B-1609.6.4.4.1 COMPONENTS
 AND CLADDING. WIND PRESSURE FOR EACH COMPONENT OR
 CLADDING ELEMENT IS TO BE DESIGNED FOR WIND PRESSURES
 COMPONENTS AND ATTACHMENTS.
  
 20) 045 M-410 ROOF DUCT SUPPORT AND RAISED ROOF TOP
 MOUNTED MECHANICAL EQUIPMENT ARE TO MEET THE
 REQUIREMENTS FOUND IN TABLE 1510.10 OF THE 2020
 FBC-BUILDING CODE.
  
 21) PLEASE PROVIDE DETAILS FOR CUTTING FOR PENETRATIONS
 FOR NEW HOLES IN THE 2ND FLOOR SLAB AND ROOF DECK. 2020
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. CONSTRUCTION DOCUMENTS SHALL
 BE SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 22) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  