| 2023-01-18 11:36:25 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 23010061 |
| | ADD: 700 S ROSEMARY AVE # 124 |
| | CONT: JONATHAN ANDREW CONSTRUCTION INC. |
| | TEL: 305-661-9500 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JAN. 18TH/ 2023 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 029 LS-1 THE LIFE SAFETY PLAN. THE LIFE SAFETY |
| | PLAN INDICATES THERE ARE 5 EXITS. EXITS 2, 4 & 5 MEET |
| | THE REQUIREMENTS FOR EXITS, A MEANS OF EGRESS. PLEASE |
| | REVIEW IN THE 2020 FBC-BUILDING CODE 1010.1.2 EGRESS |
| | DOORS SHALL BE OF THE PIVOTED OR SIDE HINGED SWINGING |
| | TYPE, ALSO SEE EXCEPTIONS. EXIT # 4 IS THE POWER |
| | SLIDING GLASS DOORS, THIS TYPE OF DOOR WILL ALSO NEED |
| | TO COMPLY WITH 1010.1.4.3. EXITS 1 & 3 ACCORDION |
| | HORIZONTAL DOORS DOES MEET THE INTENT OF SECTION |
| | 1010.1.4.3. EXIT 2 & 4 MEET THE OCCUPANT LOADS STATED. |
| | EXITS 2 & 4 ALSO MEET THE ?? THE DIAGONAL DISTANCE |
| | APART FOR THE ROOM SERVED. |
| | |
| | 2A) SHEET 029 LS-1 THE LIFE SAFETY PLAN & SHEET 001 A-1 |
| | PARTITION PLAN SHOW A PRIVATE DINING ROOM, ROOMS ARE |
| | NOT IDENTIFIED WITH ROOM NUMBERS. THE DINING ROOM HAS |
| | 14 SEATS AROUND THE TABLE AND ENTRY THROUGH DOOR # 07 |
| | HIDDEN TOP AND BOTTOM TRACKS. PLEASE REVIEW THE 2020 |
| | FBC-BUILDING CODE1010.1.2 EXCEPTION # 9 MANUALLY |
| | OPERATED HORIZONTAL SLIDING DOOR ARE PERMITTED IN A |
| | MEANS OF EGRESS FROM SPACES WITH AN OCCUPANT LOAD OF 10 |
| | OR LESS. |
| | |
| | 2B) SHEET 029 LS-1 THE LIFE SAFETY PLAN & SHEET 001 A-1 |
| | PARTITION PLAN SHOW A PRIVATE DINING ROOMS WITH DOOR |
| | OPENINGS 7 & 8. THE DOOR SCHEDULE SHEET 005 A1.2 LIST |
| | THESE DOOR TYPES AS DOOR TYPE 3 SLIDING DOOR ASSEMBLY |
| | HIDDEN TOP AND BOTTOM TRACK. PLEASE SHOW COMPLIANCE |
| | WITH THE 2020 FBC-ACCESSIBILITY CODE SECTION 302.2. |
| | OPENINGS IN THE FLOOR. THIS COMMENT HOLDS FOR ALL DOORS |
| | WITH BOTTOM TRACKS. |
| | |
| | 3A) SHEET 029 LS-1 THE LIFE SAFETY PLAN & SHEET 001 A-1 |
| | PARTITION PLAN SHOW A PRIVATE DINING ROOM, ROOMS ARE |
| | NOT IDENTIFIED WITH ROOM NUMBERS. THE PRIVATE DINING |
| | ROOM IN FRONT OF THE JUST ADDRESSED ABOVE HAS |
| | APPROXIMATELY 22 SEATS WITH TABLES AND ENTRY THROUGH |
| | DOOR # 08 IT APPEARS BARN STYLE DOORS. DOOR STYLE # 3 |
| | HIDDEN TOP AND BOTTOM TRACKS. PLEASE REVIEW THE 2020 |
| | FBC-BUILDING CODE1010.1.2 EXCEPTION # 9 MANUALLY |
| | OPERATED HORIZONTAL SLIDING DOOR ARE PERMITTED IN A |
| | MEANS OF EGRESS FROM SPACES WITH AN OCCUPANT LOAD OF 10 |
| | OR LESS. |
| | |
| | 3B) THERE APPEARS TO BE ANOTHER SET OF DOORS INTO THIS |
| | SPACE, THIS OPENING IS NOT IDENTIFIED WITH A DOOR |
| | IDENTIFICATION TAG, BUT THE PLAN SHOWS A PAIR OF SWING |
| | DOORS. AS SHOWN THE DOORS DO NOT TOTALLY ENCLOSE THIS |
| | DINING ROOM. 2020 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. |
| | |
| | 4) THERE IS A THIRD PRIVATE DINING ROOM ACROSS THE MAIN |
| | DINING ROOM, AGAIN ROOMS DO NOT HAVE IDENTIFICATION |
| | TAGS, DOOR # 9 DOOR STYLE 3 HIDDEN TOP AND BOTTOM |
| | TRACKS. PLEASE REVIEW THE 2020 FBC-BUILDING |
| | CODE1010.1.2 EXCEPTION # 9 MANUALLY OPERATED HORIZONTAL |
| | SLIDING DOOR ARE PERMITTED IN A MEANS OF EGRESS FROM |
| | SPACES WITH AN OCCUPANT LOAD OF 10 OR LESS. |
| | |
| | 5) SHEET 029 LS-1 THE LIFE SAFETY PLAN SHOWS THE |
| | ACCESSIBLE WHEELCHAIR LOCATIONS BUT NOT WITH THE |
| | REQUIRED CLEAR FLOOR SPACE. 2020 FBC-ACCESSIBILITY CODE |
| | 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR SPACE |
| | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH |
| | SHALL BE PROVIDED. KNEE AND TOE CLEARANCE COMPLYING |
| | WITH 306 SHALL BE PROVIDED. |
| | |
| | 6A) SHEET 001 A-1 SHOWS DETAIL S/A-1.1, THIS IS THE |
| | DROPPED SECTION OF THE BAR FOR ACCESSIBILITY. THE |
| | DETAIL LACKS SHOWING CLEAR FLOOR OR GROUND SPACE |
| | SECTION 902.2 OF THE 2020 FBC-ACCESSIBILITY CODE. A |
| | CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A |
| | FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE |
| | CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 6B) BAR DETAILS WILL NEED TO SHOW COMPLIANCE WITH THE |
| | 2020 FBC-ACCESSIBILITY CODE SECTIONS: |
| | 306.2 TOE CLEARANCE306.2.2 MAXIMUM DEPTH 306.2.3 |
| | MINIMUM DEPTH 306.2.4 & 306.2.5 AND |
| | 306.3 KNEE CLEARANCE. 306.3.1-306.3.5. |
| | |
| | 7A) SHEET 029 LIFE SAFETY PLAN SHOWS ACCESSIBLE SEATING |
| | JUST TO THE RIGHT OF EXIT # 4 ON THE EXTERIOR OF THE |
| | BUILDING. SHEET 001 A-1 THE PARTITION PLAN SHOWS A |
| | DETAIL FOR THIS AREA, DETAIL B/A-1.1. THE DETAIL |
| | INDICATES ON THE EXTERIOR SIDE THE HEIGHT OF THE |
| | COUNTERTOP IS 42 INCHES IN HEIGHT. THIS HEIGHT DOES NOT |
| | COMPLY WITH 902.3 HEIGHT. THE TOPS OF DINING SURFACES |
| | AND WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 7B) FIXED WALL TYPE COUNTERTOP DETAILS WILL NEED TO |
| | SHOW COMPLIANCE WITH THE 2020 FBC-ACCESSIBILITY CODE |
| | SECTIONS: |
| | 306.2 TOE CLEARANCE306.2.2 MAXIMUM DEPTH 306.2.3 |
| | MINIMUM DEPTH 306.2.4 & 306.2.5 AND |
| | 306.3 KNEE CLEARANCE. 306.3.1-306.3.5. |
| | |
| | 8) COMPONENTS & CLADDING. PLEASE SUBMIT THE COMPONENTS |
| | AND CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| | CONCRETE INSULATION, ROOF TOP VENTILATORS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 9) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP |
| | DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD |
| | PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. |
| | |
| | 10) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING |
| | DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE |
| | DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| | REVIEW. |
| | |
| | 11) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE |
| | OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR |
| | REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER???S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 12) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 13) THE ARCHITECTURAL & STRUCTURAL SHEETS SHOW WELDED |
| | STEEL CONNECTIONS. WELDED OR BOLTED CONNECTIONS. THIS |
| | BUILDING CONTAINS EITHER BOLTED AND OR WELDED |
| | CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD |
| | PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON |
| | THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL |
| | BE REQUIRED. |
| | THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO |
| | COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS |
| | SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING |
| | INSPECTION. |
| | 2020 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR RICHARD |
| | BRUNELLE AT 561-805-6670. |
| | |
| | 14A) SHEET 006 A-1.2 DETAIL A SHOWS THE USE OF A NEW |
| | FOLDING DOOR, CROWN DOOR OR EQUAL. 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1. DRAWINGS & SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC TO THE TECHNICAL CODES |
| | "CODE SECTIONS SHALL NOT BE CITED AS A WHOLE OR IN |
| | PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS |
| | A SUBSTITUTE FOR SPECIFIC INFORMATION". |
| | |
| | 14B) PLEASE PROVIDE DOCUMENTATION WHERE THE NEW FOLDING |
| | DOOR MEETS THE REQUIREMENTS FOR SLOPED GLAZING IN |
| | ACCORDANCE WITH 2405.2 OF THE 2020 FBC-BUILDING CODE. |
| | |
| | 15) SHEET 028 G-1 NOTES AND FINISHES. WATER CLOSET GRAB |
| | BARS. THE REAR GRAB BAR HEIGHT IS GIVEN 32-36 INCHES |
| | FROM CENTERLINE FROM FINISH FLOOR. SIDE WALL GRAB BAR |
| | 33-36 INCHES CENTERLINE. 2020 FBC-ACCESSIBILITY CODE |
| | SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE |
| | INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM |
| | AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED |
| | TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE. |
| | |
| | 16A) I???VE LOCATED THE RESTROOM ELEVATION PLANS A-1.3- |
| | A-1.5. I SEE WALL TAGS FOR ROOM FINISHES BUT I DO NOT |
| | FIND THE KEY OR SCHEDULE TO IDENTIFY WALL AND FLOOR |
| | FINISHES. 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS |
| | COMMENT IS A RESULT OF THE BUILDING OFFICIAL |
| | INTERPRETATION ON 06/2020. IN BATHROOMS, RESTROOMS & |
| | SERVICE SINK AREAS EPOXY PAINT IS NO LONGER CONSIDERED |
| | A SMOOTH HARD, NON-ABSORBENT SURFACE. |
| | |
| | 16B) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF |
| | SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A |
| | SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT |
| | LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL |
| | ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A |
| | TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | |
| | 17) SHEET 056 S1.00 STATEMENT ON FLOOR PLAN. FOUNDATION |
| | DESIGN FOR CANOPY STRUCTURE PENDING REACTIONS FROM |
| | SPECIALTY ENGINEER & COORDINATE WITH UNDERGROUND |
| | UTILITIES. NO INFORMATION HAS BEEN PROVIDED. CANOPY |
| | WILL BE UNDER SEPARATE PERMIT. 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 18) SHEET 057 S1.01 THE SECOND FLOOR FRAMING PLAN FLOOR |
| | PENETRATIONS & 060 S2.01 DETAILS. STATEMENT ON PLANS. |
| | SEE MECHANICAL DRAWINGS FOR THE EXACT SHAFT SIZE AND |
| | LOCATION. PLEASE PROVIDE LOCATION. AND SIZE BUT ALSO |
| | THE MATERIAL THE PROPOSED SHAFTS ARE GOING TO BE MADE |
| | OF. 2020 FBC-BUILDING SECTIONS: |
| | 713.2 CONSTRUCTION |
| | 713.3.MATERIAL |
| | 713.4 FIRE-RESISTANCE RATING |
| | 713.5 CONTINUITY |
| | |
| | 19) THE STRUCTURAL SHEETS HAVE NO DETAILS FOR ROOF TOP |
| | CURB CONNECTIONS TO THE ROOF FRAMING NOR THE ROOF TOP |
| | EXHAUST FANS TO THE CURB. |
| | 2020 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, BUILDING.FBC-B-1609.6.4.4.1 COMPONENTS |
| | AND CLADDING. WIND PRESSURE FOR EACH COMPONENT OR |
| | CLADDING ELEMENT IS TO BE DESIGNED FOR WIND PRESSURES |
| | COMPONENTS AND ATTACHMENTS. |
| | |
| | 20) 045 M-410 ROOF DUCT SUPPORT AND RAISED ROOF TOP |
| | MOUNTED MECHANICAL EQUIPMENT ARE TO MEET THE |
| | REQUIREMENTS FOUND IN TABLE 1510.10 OF THE 2020 |
| | FBC-BUILDING CODE. |
| | |
| | 21) PLEASE PROVIDE DETAILS FOR CUTTING FOR PENETRATIONS |
| | FOR NEW HOLES IN THE 2ND FLOOR SLAB AND ROOF DECK. 2020 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1. |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. CONSTRUCTION DOCUMENTS SHALL |
| | BE SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 22) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT |
| | REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. |
| | |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |