| 2023-01-09 10:24:11 | FIRE PROVISO COMMENTS: | | | | | | (1) A PLACARD SHALL BE CONSPICUOUSLY PLACED NEAR EACH | | | EXTINGUISHER THAT STATES THAT THE FIRE PROTECTION | | | SYSTEM SHALL BE ACTIVATED PRIOR TO USING THE FIRE | | | EXTINGUISHER. | | | | | | (2) UPON ACTIVATION OF AN AUTOMATIC FIRE-EXTINGUISHING | | | SYSTEM, AN AUDIBLE ALARM OR VISUAL INDICATOR SHALL BE | | | PROVIDED TO SHOW THE SYSTEM HAS ACTIVATED. | | | | | | | | | (3) AT LEAST ONE MANUAL ACTIVATION DEVICE SHALL BE | | | LOCATED A MINIMUM OF 10 FT. AND A MAXIMUM OF 20 FT. | | | FROM THE PROTECTED HOOD EXHAUST SYSTEM(S) WITHIN A PATH | | | OF EGRESS. | | | | | | (4) INSTRUCTIONS FOR MANUALLY OPERATING THE FIRE | | | EXTINGUISHING SYSTEM SHALL BE POSTED CONSPICUOUSLY IN | | | THE KITCHEN AND SHALL BE REVIEWED WITH EMPLOYEES BY THE | | | MANAGEMENT. | | | | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|