Plan Review Notes
Plan Review Notes For Permit 23010049
Permit Number 23010049
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-01-09 10:24:11FIRE PROVISO COMMENTS:
  
 (1) A PLACARD SHALL BE CONSPICUOUSLY PLACED NEAR EACH
 EXTINGUISHER THAT STATES THAT THE FIRE PROTECTION
 SYSTEM SHALL BE ACTIVATED PRIOR TO USING THE FIRE
 EXTINGUISHER.
  
 (2) UPON ACTIVATION OF AN AUTOMATIC FIRE-EXTINGUISHING
 SYSTEM, AN AUDIBLE ALARM OR VISUAL INDICATOR SHALL BE
 PROVIDED TO SHOW THE SYSTEM HAS ACTIVATED.
  
  
 (3) AT LEAST ONE MANUAL ACTIVATION DEVICE SHALL BE
 LOCATED A MINIMUM OF 10 FT. AND A MAXIMUM OF 20 FT.
 FROM THE PROTECTED HOOD EXHAUST SYSTEM(S) WITHIN A PATH
 OF EGRESS.
  
 (4) INSTRUCTIONS FOR MANUALLY OPERATING THE FIRE
 EXTINGUISHING SYSTEM SHALL BE POSTED CONSPICUOUSLY IN
 THE KITCHEN AND SHALL BE REVIEWED WITH EMPLOYEES BY THE
 MANAGEMENT.
  
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  