| Plan Review Notes For Permit 23010048 |
| Permit Number |
23010048 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-01-13 10:14:06 | 1ST REVIEW FMC | | | PERMIT: 23010048 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET 1 OF 5: UNDER THE AIR BALANCE REPORT; A NOTE | | | STATES ??? BUILDING HVAC SYSTEM TO PROVIDE MORE THAN | | | 600 CFM TO INSURE OVERALL BUILDING BALANCE IS POSITIVE. | | | PROVIDE THE BUILDING MECHANICAL SYSTEM CALCULATIONS | | | SHOWING THAT THE SYSTEM CAN PRODUCE THE REQUIRED | | | ADDITIONAL AIR FOR THIS HOOD SYSTEM. FBC 107.3.5 | | | | | | 2) SHEET 2 OF 5: EXPLAIN THE USE OF THE 2 - 5 TON | | | CONDENSING UNITS. | | | | | | 3) PROVIDE A DEMO DRAWING OF WHAT IS TO BE REMOVED. | | | FBC 107.3.5 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|