| Plan Review Notes For Permit 23010042 |
| Permit Number |
23010042 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-03-06 11:06:15 | TO ANSWER YOUR QUESTION: | | | | | | [A] 102.1 GENERAL. WHERE THERE IS A CONFLICT BETWEEN A | | | GENERAL | | | REQUIREMENT AND A SPECIFIC REQUIREMENT, THE SPECIFIC | | | REQUIREMENT SHALL BE APPLICABLE. WHERE, IN ANY SPECIFIC | | | CASE, | | | DIFFERENT SECTIONS OF THIS CODE SPECIFY DIFFERENT | | | MATERIALS, | | | METHODS OF CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | | RESTRICTIVE SHALL GOVERN. | | | | | | WHEN THERE ARE TWO MATERIALS BEING USED, THERE ARE TWO | | | DIFFERENT TABLES. THE MORE RESTRICTIVE TABLE MUST BE | | | USED. YOU CANNOT GET MORE FLOW FROM ONE SECTION OF PIPE | | | AND LESS FLOW FROM ANOTHER SECTION OF PIPE AND | | | EFFECTIVELY SIZE THE PIPING SYSTEM USING THE LONGEST | | | RUN METHOD OR BRANCH METHOD. CSST HAS MORE FRICTION AND | | | LOSS THAN METALLIC PIPE. USING THE SAME PRESSURRES AND | | | PIPE SIZES SHOWS THAT CSST HAS LESS OUTPUT THAN | | | METALLIC PIPE. YOU MUST USE THE MORE RESTRICTIVE TABLE. | | | | | | IT CONTINUES IN THE APPENDIX THAT EXPLAINS PIPE SIZING | | | AND DESCRIBES ONLY USING "ONE LINE FROM ONE SIZING | | | TABLE" FOR EACH SYSTEM (WHICH IS FROM REGULATOR TO | | | REGULATOR). | | | | | | WITH THAT BEING SAID, USING TABLE 402.4(5), AT 125 FT | | | (THE NEXT LINE CONSIDERING THE LONGEST RUN IS 120) THE | | | MAXIMUM LOAD ALLOWED FOR 1/2" PIPE IS 414K BTU, AND YOU | | | ARE RUNNING 689K BTU. REGARDLESS OF THE ABOVE | | | MENTIONED, YOU ARE UNDERSIZED. |
|