Plan Review Notes
Plan Review Notes For Permit 23010042
Permit Number 23010042
Review Stop G
Sequence Number 1
Notes
Date Text
2023-02-28 10:00:071ST GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FRC G2413.4.1 - WHEN COMBINING MATERIALS SUCH
 AS CSST AND GALVANIZED, AND USING THE LONGEST RUN
 METHOD, YOU CAN ONLY USE ONE SIZING CHART PER "SYSTEM".
 THE 2 POUND SYSTEM USING CHART 402.4(18), IT APPEARS
 YOU ARE UNDERSIZED FOR THE BTU LOAD. (USING THE 150FT
 LINE ON THE CHART). COMPARE THE 2 CHARTS AND USE THE
 MOST RESTRICTIVE.
 A) THE 1ST LEG HAS 689K BTU - AND THE SIZE CHART SAYS
 YOU WOULD HAVE TO HAVE 1" ALL THE WAY TO THE POOL
 HEATER.
 B) AFTER THE POOL HEATER, YOU WOULD NEED AT LEAST 3/4"
 GOING UP THE WALL.
 C) YOU WOULD ALSO NEED 3/4" ALL THE WAY TO THE TWH
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  