| 2023-02-28 10:00:07 | 1ST GAS REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2020 FRC G2413.4.1 - WHEN COMBINING MATERIALS SUCH | | | AS CSST AND GALVANIZED, AND USING THE LONGEST RUN | | | METHOD, YOU CAN ONLY USE ONE SIZING CHART PER "SYSTEM". | | | THE 2 POUND SYSTEM USING CHART 402.4(18), IT APPEARS | | | YOU ARE UNDERSIZED FOR THE BTU LOAD. (USING THE 150FT | | | LINE ON THE CHART). COMPARE THE 2 CHARTS AND USE THE | | | MOST RESTRICTIVE. | | | A) THE 1ST LEG HAS 689K BTU - AND THE SIZE CHART SAYS | | | YOU WOULD HAVE TO HAVE 1" ALL THE WAY TO THE POOL | | | HEATER. | | | B) AFTER THE POOL HEATER, YOU WOULD NEED AT LEAST 3/4" | | | GOING UP THE WALL. | | | C) YOU WOULD ALSO NEED 3/4" ALL THE WAY TO THE TWH | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | |
|