2023-05-02 14:24:034TH REVIEW FMC
 PERMIT: 23010039
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SCOPE OF WORK ON THE MECHANICAL DRAWING
 INDICATES THERE TO BE ENERGY CALCS AND LOAD SIZING
 CALCS FOR THE MECHANICAL, THESE WERE NOT IN THIS
 SUBMITTAL. PLEASE SUBMIT THESE IN THE NEXT REVIEW
 CYCLE.
  
 2) LABEL EACH ROOM OF THE HOME ON THE MECHANICAL
 DRAWING. IT IS UNCLEAR TO THIS REVIEWER IF THE GARAGE
 HAS BEEN CONVERTED INTO CONDITIONED SPACE. IF IT IS
 STILL A GARAGE REMOVE THE SUPPLY AIR FROM THE GARAGE AS
 THE MECHANICAL SYSTEM CANNOT SUPPLY AIR TO THE GARAGE.
 FRC M1601.6
  
 3) PROVIDE A RETURN AIR PATH FROM THE BEDROOM BACK TO
 THE AHU WHEN THE BEDROOM DOORS ARE CLOSED. FRC M1602.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  