| Plan Review Notes For Permit 23010039 |
| Permit Number |
23010039 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2023-05-02 14:24:03 | 4TH REVIEW FMC | | | PERMIT: 23010039 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE SCOPE OF WORK ON THE MECHANICAL DRAWING | | | INDICATES THERE TO BE ENERGY CALCS AND LOAD SIZING | | | CALCS FOR THE MECHANICAL, THESE WERE NOT IN THIS | | | SUBMITTAL. PLEASE SUBMIT THESE IN THE NEXT REVIEW | | | CYCLE. | | | | | | 2) LABEL EACH ROOM OF THE HOME ON THE MECHANICAL | | | DRAWING. IT IS UNCLEAR TO THIS REVIEWER IF THE GARAGE | | | HAS BEEN CONVERTED INTO CONDITIONED SPACE. IF IT IS | | | STILL A GARAGE REMOVE THE SUPPLY AIR FROM THE GARAGE AS | | | THE MECHANICAL SYSTEM CANNOT SUPPLY AIR TO THE GARAGE. | | | FRC M1601.6 | | | | | | 3) PROVIDE A RETURN AIR PATH FROM THE BEDROOM BACK TO | | | THE AHU WHEN THE BEDROOM DOORS ARE CLOSED. FRC M1602.3 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|