Plan Review Notes
Plan Review Notes For Permit 23010039
Permit Number 23010039
Review Stop E
Sequence Number 2
Notes
Date Text
2023-05-08 15:37:47FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 NOTES:
  
 1. ELECTRICAL DRAWINGS ARE ON PAGE 5.
  
 2. PROVIDE DISCONNECTING MEANS FOR A/C EQUIPMENT PER
 NEC 440.14 OR IRC E4101.5
 DISCONNECTING MEANS IS REQUIRED TO BE LOCATED, WITHIN
 SIGHT FROM AND READILY ACCESSIBLE FROM THE
 AIR-CONDITIONING EQUIPMENT.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER/ INSPECTOR
 561-805-6738
 [email protected]