| Plan Review Notes For Permit 23010038 |
| Permit Number |
23010038 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-01-24 10:41:06 | FIRE REVIEW: | | | | | | THE SUBMITTAL DID NOT DESCRIIBE THE TYPE OF FLOORING TO | | | BE INSTALLED. IF THE FINISH FLOOR IS A COMBUSTIBLE | | | MATERIAL (VINYL, CARPET, ETC.) THE SUBMITTAL SHALL | | | INCLUDE THE MATERIALS FIRE PERFORMANCE TEST DATA TO | | | INCLUDE THE CRITICAL RADIAT FLUX OF THE MATERIALS. THIS | | | APPLIES TO THE FINISHED FLOORING AND THE UNDERLAYMENT. | | | NFPA 101, 10.2.7 | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|