| 2023-01-23 15:31:24 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. PROVIDE SIZE OF EQUIPMENT GROUNDING CONDUCTORS FROM | | | NEW 200 AMPS METER CAN TO NEW 200 AMPS 40 CKT MB PANEL | | | AND FROM THE NEW 200 AMPS 40 CKT MB PANEL TO THE | | | EXISTING INDOOR SUBPANEL IN ACCORDANCE WITH NEC 250, | | | NEC TABLE | | | 250.122 | | | | | | END OF COMMENTS | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | [email protected] | | | |
|