| Plan Review Notes For Permit 22121381 |
| Permit Number |
22121381 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2023-04-19 14:50:59 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PRODUCT APPROVAL PROVIDED FOR THE SLIDING GLASS DOOR | | | (20-0429.09) DOES NOT MEET THE REQUIRED WIND PRESSURES | | | FOR DOORS ED-102, ED-108, ED-201, ED-205 IN WIND ZONE 5 | | | SEE DRAWING S0.2 ZONE 5. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|