| 2023-01-27 08:07:17 | NEW SFR |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVAL FOR THE ROOFING SYSTEMS - REVIEWED AND |
| | MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD FBC |
| | WPB 107.3.4 (PLEASE CIRCLE THE ROOFING SYSTEM IN THE |
| | PRODUCT APPROVAL THAT IS TO BE USED) |
| | |
| | 2) PLEASE SHOW THAT TERMITE PROTECTION IS REQUIRED - |
| | FBC R318 |
| | |
| | 3) PRODUCT APPROVAL PROVIDED FOR THE SLIDING GLASS DOOR |
| | (20-0429.09) DOES NOT MEET THE REQUIRED WIND PRESSURES |
| | FOR WIND ZONE 5 SEE DRAWING S0.2 ZONE 5. |
| | |
| | 4) PLEASE PROVIDE AN INSWING DOOR PRODUCT APPROVAL FOR |
| | THE POOL BATH ENTRY DOOR AND THE GARAGE MAN DOOR. |
| | |
| | 5) PLEASE SHOW THE ATTIC VENTILATION ON THE DRAWINGS AS |
| | THE PROVIDED ENERGY CALCULATIONS SHOW "R" 30 WITH |
| | VENTILATION. FBC R806 |
| | |
| | 6) PLEASE SHOW THE STORM WATER DRAINAGE FLOW AWAY FROM |
| | THE BUILDING AND AWAY FROM ADJACENT PROPERTY ON THE |
| | SITE PLAN OR PROVIDE A STORM WATER DRAINAGE PLAN - FBC |
| | WPB 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS |
| | SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE |
| | ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE |
| | AND LOCATION OF NEW CONSTRUCTION AND EXISTING |
| | STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE |
| | ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED |
| | GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS |
| | APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN |
| | FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE |
| | WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE |
| | SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED |
| | WATER RETAINING SWALES) |
| | |
| | 7) FYI - SEPARATE PERMITS ARE REQUIRED FOR FENCE, |
| | DRIVEWAY, POOL |