| 2023-02-10 15:17:47 | NEW SFR |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) DRAWING CS0.00 - SHOWS THE 2017 FBC USED - NEEDS TO |
| | BE PER 2020 FBC |
| | |
| | 2) PLEASE SHOW THE ATTIC ACCESS LOCATION AND SIZE PER |
| | FBC R807.1 |
| | |
| | 3) PLEASE PROVIDE AN INTERIOR DOOR SCHEDULE - FBC |
| | R320.1.1 |
| | ALL NEW SINGLE-FAMILY HOUSES, DUPLEXES, TRIPLEXES, |
| | CONDOMINIUMS AND TOWNHOUSES SHALL PROVIDE AT LEAST ONE |
| | BATHROOM, LOCATED WITH MAXIMUM POSSIBLE PRIVACY, WHERE |
| | BATHROOMS ARE PROVIDED ON HABITABLE GRADE LEVELS, WITH |
| | A DOOR THAT HAS A 29-INCH (737 MM) CLEAR OPENING. |
| | HOWEVER, IF ONLY A TOILET ROOM IS PROVIDED AT GRADE |
| | LEVEL, SUCH TOILET ROOMS SHALL HAVE A CLEAR OPENING OF |
| | NOT LESS THAN 29 INCHES |
| | |
| | 4) WINDOW AND DOOR PRODUCT APPROVALS NEED TO BE |
| | REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER |
| | OF RECORD - FBC WPB 107.3.4 |
| | |
| | 5) HARDI - BOARD SIDING IS SUBJECT TO WIND LOADS - |
| | PLEASE PROVIDE ATTACHMENT DETAILS ON THE DRAWINGS OR |
| | PROVIDE A PRODUCT APPROVAL FOR THE HARDI - BOARD SIDING |
| | - FBC R703.1.2 |
| | |
| | 6) PLEASE PROVIDE THE ICC EVALUATION REPORT FOR THE |
| | ICYNENE FOAM INSULATION - FBC R316 |
| | |
| | 7) PLEASE SHOW ON THE SITE PLAN THE STORM WATER FLOW |
| | AWAY FROM THE BUILDING AND AWAY FROM THE ADJACENT |
| | PROPERTY OR PROVIDE A STORM WATER PLAN - FBC WPB |
| | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| | DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES |
| | AND THE PROPOSED FINISHED GRADES, DEPICTING THE |
| | PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD |
| | AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT |
| | SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| | INCLUDED ON A BOUNDARY LINE SURVEY. (PLEASE PROVIDE CUT |
| | SECTIONS FOR ANY PROPOSED WATER RETAINING SWALES) |
| | |
| | 8) SIGNED AND SEALED DRAWINGS DO NOT SHOW AS DIGITALLY |
| | SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN |
| | PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED |
| | TO BE USED IN ELECTRONIC PLAN REVIEW. (A |
| | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED |
| | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF |
| | E-SIGNATURE). |
| | |
| | 9) PLEASE PROVIDE A SURVEY. |