Plan Review Notes
Plan Review Notes For Permit 22121339
Permit Number 22121339
Review Stop P
Sequence Number 1
Notes
Date Text
2023-01-18 13:52:011ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22121339
 1/18/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENERGY FORM R405-2020 DOES NOT LIST COMPLIANCE
 DATA FOR THE HOT WATER SYSTEMS- SEC. R403.5.6.2 & TABLE
 C404.2 FBC EC.
  
 2) P-2 & A.2.3: THE CHRONOMITE TANKLESS WATER HEATER IS
 BEING INSTALLED IN THE TRELLISED ACCESSORY STRUCTURE
 WHICH IS NOT PROTECTED FROM RAIN AND STORMWATERS.
 PLEASE SUBMIT MANUFACTURER???S SPECIFICATIONS VERIFYING
 THE UNIT CAN BE INSTALLED IN THIS LOCATION- SEC.
 107.2.1 WPB. PLEASE NOTE THE MANUFACTURER MAY REQUIRE
 THE UNIT TO BE INSTALLED IN A WEATHERTIGHT, WATERPROOF
 ENCLOSURE.
  
 3) P-2 & A.2.3: THE PLUMBING FLOOR PLAN INDICATES A
 BATHROOM IN THE TRELLISED ACCESSORY STRUCTURE. THIS
 APPEARS TO BE A PLAN ERROR, PLEASE CORRECT- SEC.
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  