| 2023-01-18 13:52:01 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 22121339 | | | 1/18/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE ENERGY FORM R405-2020 DOES NOT LIST COMPLIANCE | | | DATA FOR THE HOT WATER SYSTEMS- SEC. R403.5.6.2 & TABLE | | | C404.2 FBC EC. | | | | | | 2) P-2 & A.2.3: THE CHRONOMITE TANKLESS WATER HEATER IS | | | BEING INSTALLED IN THE TRELLISED ACCESSORY STRUCTURE | | | WHICH IS NOT PROTECTED FROM RAIN AND STORMWATERS. | | | PLEASE SUBMIT MANUFACTURER???S SPECIFICATIONS VERIFYING | | | THE UNIT CAN BE INSTALLED IN THIS LOCATION- SEC. | | | 107.2.1 WPB. PLEASE NOTE THE MANUFACTURER MAY REQUIRE | | | THE UNIT TO BE INSTALLED IN A WEATHERTIGHT, WATERPROOF | | | ENCLOSURE. | | | | | | 3) P-2 & A.2.3: THE PLUMBING FLOOR PLAN INDICATES A | | | BATHROOM IN THE TRELLISED ACCESSORY STRUCTURE. THIS | | | APPEARS TO BE A PLAN ERROR, PLEASE CORRECT- SEC. | | | 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|