| Plan Review Notes For Permit 22121339 |
| Permit Number |
22121339 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-01-23 10:46:40 | ELECTRIC REVIEW FAILED | | | | | | 1) ADDITIONAL STRUCTURE DOES NOT COMPLY WITH NEC | | | ARTICLE 225 OUTSIDE BRANCH CIRCUITS AND FEEDERS. PLEASE | | | CORRECT AS APPLICABLE | | | | | | BUILDINGS OR OTHER STRUCTURES SUPPLIED BY A FEEDER(S) | | | OR BRANCH CIRCUIT(S) | | | NEC 225.30 NUMBER OF SUPPLIES. | | | A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A | | | BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE | | | DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE | | | FEEDER OR BRANCH CIRCUIT | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | | | | |
|