2023-07-20 10:02:181ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22121291
 7/20/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P101A: PROVIDE A VENT FOR THE FLOOR DRAIN IN THE PET
 WASH 129 ROOM- SEC. 901.2.1 FBC P.
  
 2) P310: CONCERNING THE USE OF THE SOVENT SYSTEM, THE
 SYSTEM IS DEFINED AS AN ALTERNATIVE ENGINEERED DESIGN
 WHICH REQUIRES THE ENGINEER OF RECORD TO SUBMIT
 TECHNICAL DATA TO SUBSTANTIATE THE PROPOSED ALTERNATIVE
 DESIGN AND TO PROVE THE PERFORMANCE MEETS THE INTENT OF
 THE CODE- SEC. 316.1.3. PLEASE PROVIDE THE FOLLOWING
 ITEMS-
  
 A) ENGINEER'S LETTER TO THE BUILDING OFFICIAL WITH
 SUFFICIENT EVIDENCE TO REQUEST APPROVAL OF THE
 ALTERNATIVE SYSTEM.
  
 B) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS WITH ENGINEER'S APPROVAL STAMP.
  
 C) SITE SPECIFIC INSTALLATION DETAILS ON THE PLANS.
  
 D) REVISED RISER DRAWINGS. THE REVISED SHEET 310 SHOWS
 SOVENT DEAERATORS INSTALLED AT RISERS SS-1, 6, 8, 12,
 15, 18, 22, 25, 27, 28, 33, 41, 54, 60, 62, 66, 69, 72
 & 76. PLEASE SUBMIT REVISED RISER PLANS SHEETS P305,
 P306, P307, P308, P309 SHOWING THE NEW SOVENT
 DEAERATORS AT THE RISERS. PLEASE NOTE RELIEF VENTS ARE
 REQUIRED FOR WASTE AND SOIL STACKS HAVING MORE THAN 10
 BRANCH INTERVALS.THE REVISED DRAWINGS SHALL SHOW
 COMPLIANCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER