| 2023-07-20 10:02:18 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22121291 |
| | 7/20/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) P101A: PROVIDE A VENT FOR THE FLOOR DRAIN IN THE PET |
| | WASH 129 ROOM- SEC. 901.2.1 FBC P. |
| | |
| | 2) P310: CONCERNING THE USE OF THE SOVENT SYSTEM, THE |
| | SYSTEM IS DEFINED AS AN ALTERNATIVE ENGINEERED DESIGN |
| | WHICH REQUIRES THE ENGINEER OF RECORD TO SUBMIT |
| | TECHNICAL DATA TO SUBSTANTIATE THE PROPOSED ALTERNATIVE |
| | DESIGN AND TO PROVE THE PERFORMANCE MEETS THE INTENT OF |
| | THE CODE- SEC. 316.1.3. PLEASE PROVIDE THE FOLLOWING |
| | ITEMS- |
| | |
| | A) ENGINEER'S LETTER TO THE BUILDING OFFICIAL WITH |
| | SUFFICIENT EVIDENCE TO REQUEST APPROVAL OF THE |
| | ALTERNATIVE SYSTEM. |
| | |
| | B) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| | INSTRUCTIONS WITH ENGINEER'S APPROVAL STAMP. |
| | |
| | C) SITE SPECIFIC INSTALLATION DETAILS ON THE PLANS. |
| | |
| | D) REVISED RISER DRAWINGS. THE REVISED SHEET 310 SHOWS |
| | SOVENT DEAERATORS INSTALLED AT RISERS SS-1, 6, 8, 12, |
| | 15, 18, 22, 25, 27, 28, 33, 41, 54, 60, 62, 66, 69, 72 |
| | & 76. PLEASE SUBMIT REVISED RISER PLANS SHEETS P305, |
| | P306, P307, P308, P309 SHOWING THE NEW SOVENT |
| | DEAERATORS AT THE RISERS. PLEASE NOTE RELIEF VENTS ARE |
| | REQUIRED FOR WASTE AND SOIL STACKS HAVING MORE THAN 10 |
| | BRANCH INTERVALS.THE REVISED DRAWINGS SHALL SHOW |
| | COMPLIANCE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | |