Plan Review Notes
Plan Review Notes For Permit 22121291
Permit Number 22121291
Review Stop P
Sequence Number 2
Notes
Date Text
2023-04-24 16:56:432ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22121291
 4/24/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P101A: THE REVISED SHEET SHOWS SOME KEY ITEMS
 HAVE BEEN CHANGED OR DELETED. PLEASE PROVIDE A COMPLETE
 NARRATIVE TO CLARIFY THE FOLLOWING ITEMS.
 A) DOMESTIC AND IRRIGATION WATER SERVICE ENTRANCE
 LOCATIONS ARE NOT SHOWN.
 B) BUILDING DRAINS AND SEWER DRAIN SIZES HAVE BEEN
 REDUCED ON THE EAST SIDE.
 C) DFU CALCULATIONS HAVE BEEN REMOVED.
 D) SEWER DRAIN CLEANOUT LOCATIONS HAVE BEEN REMOVED ON
 THE EAST SIDE.
 E) FLOOR DRAIN REMOVED FROM THE PET WASH.
 F) GAS METER LOCATION REMOVED.
  
 2) P101A: BASED ON THE CHANGES SHOWN PLEASE SUBMIT A
 REVISED SANITARY ISOMETRIC DRAWING- SEC. 107.2.1 WPB.
  
 3) P105: PLEASE PROVIDE A CLOUD AND REVISION NUMBER TO
 SHOW THE LOCATION OF THE NEW PANTRY SINK ON THE FLOOR
 PLAN- SEC. 107.2.1 WPB.
  
 4) P105: PLEASE REPLACE THE REMOVED UNIT IDENTIFICATION
 NUMBERS- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  