| Plan Review Notes For Permit 22121291 |
| Permit Number |
22121291 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-01-24 10:27:37 | 1ST REVIEW FMC | | | PERMIT: 22121291 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE MECHANICAL NARRATIVE STATES EQUIPMENT WAS ADDED | | | AND SEVERAL PIECES WERE MOVED THE VALUE OF THE REVISION | | | IS LISTED AS $0, PLEASE PROVIDE THE ADDED VALUE OF | | | THESE REVISIONS. | | | | | | 2) SHEET M4-01: THERE IS NO NEW REVISED DRAWING. THE | | | SHEET SUBMITTED IS THE SAME DRAWING. THEY BOTH ARE FOR | | | REVISION 1 BDC 02-14-2022. PROVIDE THE REVISED DRAWING | | | FOR THE REVISION MENTION ON THE NARRATIVE SHEET. FBC | | | 107.3.5 | | | | | | 3) SHEET M4-02: THERE IS NO NEW REVISED DRAWING. THE | | | SHEET SUBMITTED IS THE SAME DRAWING. THEY BOTH ARE FOR | | | REVISION 1 BDC 02-14-2022. PROVIDE THE REVISED DRAWING | | | FOR THE REVISION MENTION ON THE NARRATIVE SHEET. FBC | | | 107.3.5 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|