Plan Review Notes
Plan Review Notes For Permit 22121291
Permit Number 22121291
Review Stop B
Sequence Number 1
Notes
Date Text
2023-01-25 08:35:52REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A0-102 THE ACCESSIBLE PARKING NEEDS TO BE
 NEAR THE ELEVATORS AND MATCH DRAWING A1-102 - FBC
 208.3.1
  
 2) DRAWING A1-314 - UNIT B1 813 - SHOWER DOES NOT
 APPEAR TO HAVE THE CLEAR FLOOR SPACE REQUIRED - FBC FHA
 REQUIREMENT 7 (2) (B) (VII)
  
 3) DRAWING A0-106 - THE OCCUPANT LOAD CHART SHOWS 653
 OCCUPANTS - THE DOOR OPENINGS AT 160 PERSONS EACH X 4 =
 640 WHICH DOES NOT MEET THE OCCUPANT LOAD - FBC
 1005.3.2
  
 4) DRAWING A1-324 - UNIT A3 PLEASE SHOW THE DIMENSION
 FBC FHA REQUIREMENT 7 (1) (B) CLEARANCE BETWEEN
 COUNTERS AND ALL OPPOSING BASE CABINETS, COUNTERTOPS,
 APPLIANCES OR WALLS IS AT LEAST 40 INCHES.
  
 5) DRAWING A1-325 - UNIT A4 AND A5 PLEASE SHOW THE
 DIMENSION FBC FHA REQUIREMENT 7 (1) (B) CLEARANCE
 BETWEEN COUNTERS AND ALL OPPOSING BASE CABINETS,
 COUNTERTOPS, APPLIANCES OR WALLS IS AT LEAST 40 INCHES.
  
 6) DRAWING A1-106 - FITNESS ROOM - DOOR 703B IS SHOWN
 AS 2' 8" WHICH IS NOT A USEABLE DOOR WITH A CLEAR WIDTH
 OF 32" - IT SHOULD BE A USEABLE DOOR WITH 32" CLEARANCE
 PER FBC FHA REQUIREMENT 2 (14)
  
 7) THE ARCHITECTURAL DRAWINGS - DO NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED
 DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).