| 2023-01-25 08:35:52 | REVISION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) DRAWING A0-102 THE ACCESSIBLE PARKING NEEDS TO BE |
| | NEAR THE ELEVATORS AND MATCH DRAWING A1-102 - FBC |
| | 208.3.1 |
| | |
| | 2) DRAWING A1-314 - UNIT B1 813 - SHOWER DOES NOT |
| | APPEAR TO HAVE THE CLEAR FLOOR SPACE REQUIRED - FBC FHA |
| | REQUIREMENT 7 (2) (B) (VII) |
| | |
| | 3) DRAWING A0-106 - THE OCCUPANT LOAD CHART SHOWS 653 |
| | OCCUPANTS - THE DOOR OPENINGS AT 160 PERSONS EACH X 4 = |
| | 640 WHICH DOES NOT MEET THE OCCUPANT LOAD - FBC |
| | 1005.3.2 |
| | |
| | 4) DRAWING A1-324 - UNIT A3 PLEASE SHOW THE DIMENSION |
| | FBC FHA REQUIREMENT 7 (1) (B) CLEARANCE BETWEEN |
| | COUNTERS AND ALL OPPOSING BASE CABINETS, COUNTERTOPS, |
| | APPLIANCES OR WALLS IS AT LEAST 40 INCHES. |
| | |
| | 5) DRAWING A1-325 - UNIT A4 AND A5 PLEASE SHOW THE |
| | DIMENSION FBC FHA REQUIREMENT 7 (1) (B) CLEARANCE |
| | BETWEEN COUNTERS AND ALL OPPOSING BASE CABINETS, |
| | COUNTERTOPS, APPLIANCES OR WALLS IS AT LEAST 40 INCHES. |
| | |
| | 6) DRAWING A1-106 - FITNESS ROOM - DOOR 703B IS SHOWN |
| | AS 2' 8" WHICH IS NOT A USEABLE DOOR WITH A CLEAR WIDTH |
| | OF 32" - IT SHOULD BE A USEABLE DOOR WITH 32" CLEARANCE |
| | PER FBC FHA REQUIREMENT 2 (14) |
| | |
| | 7) THE ARCHITECTURAL DRAWINGS - DO NOT SHOW AS |
| | DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED |
| | DRAWINGS IN PROJECTDOX NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN |
| | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL |
| | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A |
| | SPECIFIC TYPE OF E-SIGNATURE). |