| 2023-03-08 17:44:50 | 3RD REVIEW FMC |
| | PERMIT: 22121260 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE NEWLY ADDED DRYER DUCT MATERIAL SHALL MEET THE |
| | MATERIAL REQUIREMENTS OF FMC 504.8.1 |
| | |
| | 2) PROVIDE A DETAIL DRAWING OF THE MANICURE AND |
| | PEDICURE STATIONS EXHAUST SYSTEM, INCLUDE HOW EACH WILL |
| | BE SECURED AT EACH STATION TO MEET THE REQUIREMENTS OF |
| | FMC 502.20. |
| | |
| | 3) THE VENTILATION MUST SHOW THE REQUIRED OUTDOOR AIR |
| | AND THE REQUIRED EXHAUST FOR THIS NAIL SALON. THE NAIL |
| | SALON VENTILATION SHOULD BE CALCULATED FOR 28 PEOPLE. |
| | 28 X 20 = 560; THE SPACE IS- 1105 X .12 = 133; 560 + |
| | 133 = 693 CFM???S OF OUTDOOR AIR REQUIRED. PLEASE SHOW |
| | THE REQUIRED EXHAUST FOR THE BATH ROOMS AND THE NAIL |
| | STATIONS ??? NAIL STATIONS 663 CFM???S + BATH EXHAUST |
| | 160 CFM = 823. WHERE WILL THE MAKEUP FOR THE EXHAUST |
| | AIR COME FROM? FMC TABLE 403.3.1.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |