Plan Review Notes
Plan Review Notes For Permit 22121260
Permit Number 22121260
Review Stop M
Sequence Number 3
Notes
Date Text
2023-03-08 17:44:503RD REVIEW FMC
 PERMIT: 22121260
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE NEWLY ADDED DRYER DUCT MATERIAL SHALL MEET THE
 MATERIAL REQUIREMENTS OF FMC 504.8.1
  
 2) PROVIDE A DETAIL DRAWING OF THE MANICURE AND
 PEDICURE STATIONS EXHAUST SYSTEM, INCLUDE HOW EACH WILL
 BE SECURED AT EACH STATION TO MEET THE REQUIREMENTS OF
 FMC 502.20.
  
 3) THE VENTILATION MUST SHOW THE REQUIRED OUTDOOR AIR
 AND THE REQUIRED EXHAUST FOR THIS NAIL SALON. THE NAIL
 SALON VENTILATION SHOULD BE CALCULATED FOR 28 PEOPLE.
 28 X 20 = 560; THE SPACE IS- 1105 X .12 = 133; 560 +
 133 = 693 CFM???S OF OUTDOOR AIR REQUIRED. PLEASE SHOW
 THE REQUIRED EXHAUST FOR THE BATH ROOMS AND THE NAIL
 STATIONS ??? NAIL STATIONS 663 CFM???S + BATH EXHAUST
 160 CFM = 823. WHERE WILL THE MAKEUP FOR THE EXHAUST
 AIR COME FROM? FMC TABLE 403.3.1.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  