2023-02-14 15:15:152ND REVIEW FMC
 PERMIT: 22121260
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON TABLE
 403.3.1.1 AND NOT THE ASHRAE 62.1. THE OCCUPANT COUNT
 SHALL BE BASED FROM THE OCCUPANCY CLASSIFICATION AND
 OCCUPANCY DENSITY OF TABLE 403.3.1.1. FMC 403.3.1.1
  
 2) THERE IS NO REFERENCE IN THE 2020 FMC FOR A PORTABLE
 EXHAUST FAN, REMOVE THESE FROM THE DRAWING AND PROVIDE
 AN EXHAUST SYSTEM FOR EACH NAIL STATION THAT COMPLIES
 WITH FMC TABLE 403.3.1.1 FOOTNOTE H AND WITH FMC 502.20
  
 3) THE DRYER DUCT LENGTH, SIZE, MATERIAL AND
 TERMINATION LOCATION MUST BE INCLUDED IN THIS NEW
 TENANT DESIGN. A FLEXIBLE HOSE IS NOT AN OPTION IN THE
 2020 FMC SECTION 504
  
 4) THE CONDENSATE DRAINS SHALL NOT DRAIN TO STREET,
 ALLEY OR OTHER AREAS SO AS TO CREATE A NUISANCE. FMC
 307.2.1
  
 5) THE CONDENSATE DRAINPIPE SHALL MEET THE MATERIAL
 REQUIREMENTS OF FMC 307.2.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  