| 2023-02-14 15:15:15 | 2ND REVIEW FMC |
| | PERMIT: 22121260 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON TABLE |
| | 403.3.1.1 AND NOT THE ASHRAE 62.1. THE OCCUPANT COUNT |
| | SHALL BE BASED FROM THE OCCUPANCY CLASSIFICATION AND |
| | OCCUPANCY DENSITY OF TABLE 403.3.1.1. FMC 403.3.1.1 |
| | |
| | 2) THERE IS NO REFERENCE IN THE 2020 FMC FOR A PORTABLE |
| | EXHAUST FAN, REMOVE THESE FROM THE DRAWING AND PROVIDE |
| | AN EXHAUST SYSTEM FOR EACH NAIL STATION THAT COMPLIES |
| | WITH FMC TABLE 403.3.1.1 FOOTNOTE H AND WITH FMC 502.20 |
| | |
| | 3) THE DRYER DUCT LENGTH, SIZE, MATERIAL AND |
| | TERMINATION LOCATION MUST BE INCLUDED IN THIS NEW |
| | TENANT DESIGN. A FLEXIBLE HOSE IS NOT AN OPTION IN THE |
| | 2020 FMC SECTION 504 |
| | |
| | 4) THE CONDENSATE DRAINS SHALL NOT DRAIN TO STREET, |
| | ALLEY OR OTHER AREAS SO AS TO CREATE A NUISANCE. FMC |
| | 307.2.1 |
| | |
| | 5) THE CONDENSATE DRAINPIPE SHALL MEET THE MATERIAL |
| | REQUIREMENTS OF FMC 307.2.2 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |