| 2023-01-06 06:47:14 | 1ST PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. PAGE P-1 - 2020 FPC 912.1 - THE WATER CLOSET IS NOT |
| | SHOWN AS BEING VENTED. THE LAVATORY TYPICALLY VENTS THE |
| | WATER CLOSET FIXTURE DRAIN. ANY FIXTURES THAT ARE NOT |
| | CONSIDERED BATHROOM GROUP FIXTURES CANNOT DISCHARGE |
| | INTO THE LAV AND WATER CLOSET VENTING SYSTEM (WET |
| | VENT). ALL OTHER FIXTURES (I.E. WASHER, HAND SINK, |
| | SERVICE SINK) MUST |
| | DISCHARGE DOWNSTREAM OF THE WET VENT SYSTEM. |
| | |
| | 2. 2017 WPB AMENDS 107.3.5.1.3 - PLEASE DETAIL THE |
| | WATER PIPING SYSTEM. WHEN DETAILING THE HOT WATER |
| | SYSTEM, SHOW DETAILS THAT COMPLY WITH 2020 FPC 607.1.1 |
| | - AND 2020 FPC 607.1.2. INCLUDE A WATER HEATER DETAIL |
| | THAT INCLUDES WHERE THE T&P DISCHARGES, DRAIN PAN |
| | TERMINATION POINT, AND DISTANCE TO FARTHEST FIXTURE |
| | (NOT TO EXCEED 50 FEET WITHOUT A RECIRC LINE). |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |