2023-03-06 16:08:322ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22121209
 3/6/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENT #2 FROM THE
 1ST REVIEW IS COPIED BELOW. POINT OF USE MIXING VALVES
 AT EACH SINK ARE NOT ACCEPTABLE ALTERNATIVES TO THE
 REQUIRED MASTER THERMOSTATIC MIXING VALVE AT THE WATER
 HEATER.
  
 2) SHEETS P0.1: BECAUSE THE THERMOSTAT ON THE WATER
 HEATER CANNOT BE THE TEMPERATURE LIMITING MEANS FOR THE
 HOT WATER SYSTEM, A MASTER THERMOSTATIC MIXING VALVE IS
 REQUIRED- SEC. 607.1.1 FBC PLEASE REVISE THE WATER
 HEATER DETAIL TO SHOW THE LOCATION OF THE DEVICE AND
 PIPING CONNECTIONS- 607.2.2. ENERGY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  