| Notes |
| Date |
Text |
| 2023-03-02 11:26:47 | THIS PLAN WAS REVIEWED AND APPROVED BY CAITLIN L | | | FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING | | | COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL | | | AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE | | | FIRE SPRINKLER AND FIRE ALARM SYSTEMS FOR CODE COVERAGE | | | AND COMPLIANCE BY CERTIFIED CONTRACTORS. | | | | | | 2) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE | | | ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND | | | SHOP DRAWINGS BY CERTIFIED CONTRACTORS. | | | | | | 3) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL | | | REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION | | | PERIODS. | | | | | | | | | 4) THE DOOR SHALL SWING 180 DEGREES. 7.2.1.4.3 ANY DOOR | | | SWINGING INTO THE CORRIDOR MUST LEAVE UNOBSTRUCTED | | | DURING ITS ENTIRE SWING AT LEAST ONE HALF OF THE | | | REQUIRED CORRIDOR WIDTH. | | | | | | CAITLIN L. FRANCIS | | | FIRE INVESTIGATOR | | | WEST PALM BEACH FIRE RESCUE | | | 561-804-4728 | | | [email protected] | | | | | | |
|