Plan Review Notes
Plan Review Notes For Permit 22121209
Permit Number 22121209
Review Stop B
Sequence Number 2
Notes
Date Text
2023-03-02 10:00:56WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22121209
 ADD: 4700 N CONGRESS AVE # 201
 CONT: LEIGHTON MCGINN
 TEL: 561-348-4805
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. MAR. 02ND/ 2023
 ACTION: DENIED
  
 1) 2ND REQUEST, SEMI-COMPLIED. SHEET A120 THE EGRESS
 PLAN DOES NOT SHOW EGRESS TO THE REAR STAIRWELL FROM
 THE MAIN PORTION OF THE TENANT SUITE. THIS DOOR NEEDS
 TO SHOW THAT IT HAS 180-DEGREE HINGES TO SWING OUT OF
 THE WAY AGAINST THE WALL TO GAIN ENTRY TO STAIRWELL.
 PLANS THAT WERE NOT UPDATED STILL SHOWS A POCKET DOOR,
 SHEETS A-130, E3.1 & P2.1.
  
 2A) 2ND REQUEST. SHEET A130 DOES NOT SHOW IT WAS
 UPDATED AS STATED IN THE RESPONSE SHEET. THE RESTROOMS
 218 & 219 BOTH SHOW WALL FINISHES P-1 GENERAL WALL
 PAINT. 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS
 COMMENT IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION ON 06/2020. IN BATHROOMS, RESTROOMS &
 SERVICE SINK AREAS EPOXY PAINT IS NO LONGER CONSIDERED
 A SMOOTH HARD, NON-ABSORBENT SURFACE. 1210.2.2 WALLS &
 PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS, AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT
 SURFACE TO A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE
 FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIAL
 USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS NOT
 ADVERSELY AFFECTED BY MOISTURE.
  
 2B) 2ND REQUEST, SEMI-COMPLIED. PLEASE PROVIDE
 COMPLIANCE WITH THE 2020 FBC-BUILDING CODE TABLE 2902.1
 1 SERVICE SINK IS REQUIRED. 2020 FBC-B 1210.2.2. WALLS
 & PARTITIONS. THIS COMMENT IS A RESULT OF THE BUILDING
 OFFICIAL INTERPRETATION ON 06/2020. IN BATHROOMS,
 RESTROOMS & SERVICE SINK AREAS EPOXY PAINT IS NO LONGER
 CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE.
 2020FBC-BUILDING CODE 1210.2.2 WALLS & PARTITIONS
 WITHIN 2 FEET OF SERVICE SINKS, URINALS, AND WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT
 SURFACE TO A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE
 FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIAL
 USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS NOT
 ADVERSELY AFFECTED BY MOISTURE.
  
 3) COMPLIED, N/A DRINKING FOUNTAIN IS IN COMMON AREAS.
  
 4) 2ND REQUEST. SHEETS A201 DETAIL # 13 & A202 DETAIL #
 7 BOTH SHOW THE INSTALLATION OF A MICROWAVE, PLEASE
 PROVIDE COMPLIANCE THE RESPONSE SHEET STATES THERE IS A
 DEDICATED OUTLET FOR THE MICROWAVE AT COUNTER HEIGHT.
 THE ONLY WAY THIS WORKS IS THAT THE DESIGNER MUST STATE
 THIS ON THE PLANS: THERE WILL BE NO VISITORS TO BE ABLE
 TO USE THE EMPLOYEE BREAK ROOM, OTHERWISE THERE IS
 DISCRIMINATION TO A VISITOR IN A WHEELCHAIR. THEY ARE
 TO BE ABLE TO USE A MICROWAVE WITHOUT ANY ASSISTANCE
 FROM NO ONE!!!!! THE TENANT AS WELL AS DESIGNER OPEN
 THEMSELVES UP TO LAWSUITS WITH THE 2020
 FBC-ACCESSIBILITY CODE SECTIONS:
  
 4A) 308 REACH RANGES. 308.2 FORWARD REACH / 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. 308.3 SIDE
 REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 OBSTRUCTED HIGH
 REACH.
  
 4B) 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS
 SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 MAXIMUM.
  
 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  