| Date |
Text |
| 2023-01-20 10:11:39 | 1ST REVIEW FMC |
| | PERMIT: 22121209 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M6.1: IN THE OUTDOOR AIR CALCULATIONS PROVIDE |
| | THE CORRECT TABLE AT THE TOP OF THE CHART, TABLE |
| | 403.3.1.1 NOT 403.2.1.1. ALSO NOTE 1 OF THIS TABLE |
| | SHOULD STATE BASED OFF OF TABLE 403.3.1.1 AND NOT THE |
| | ARCHITECTURAL PLANS AS FMC 403.3.1.1 STATES WE ARE TO |
| | USE TABLE 403.3.1.1 TO DETERMINE THE OCCUPANT LOAD FOR |
| | EACH OCCUPANCY CLASSIFICATION IN THIS TENANT SPACE. |
| | |
| | 2) SHEET M6.1: OUTSIDE AIR CALCULATIONS CHART: AHU-1 |
| | INDICATES ONLY 1 OCCUPANT FOR THIS SPACE. TABLE |
| | 403.3.1.1 REQUIRES THE CALCULATIONS TO PROVIDE THE |
| | OUTDOOR AIR FOR A MINIMUM OF 19 PEOPLE FOR THIS |
| | OCCUPANCY CLASSIFICATION, WHICH WOULD REQUIRE 132 |
| | CFM???S OF OUTDOOR AIR FOR THIS SPACE. FMC 403.3.1.1 |
| | AND TABLE 403.3.1.1 |
| | |
| | 3) PROVIDE SMOKE DUCT DETECTORS FOR EACH AHU???S SUPPLY |
| | SIDE DUCT. FMC 606.2.2 |
| | |
| | 4) SIGNATURES ON THE MECHANICAL DOCUMENTS APPEAR TO BE |
| | COPIES OF THE DIGITAL SIGNATURE. PROVIDE THE ORIGINAL |
| | DIGITALLY SIGNED DOCUMENTS. FS 471/481 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |