| 2022-12-30 14:51:11 | THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L. |
| | FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING |
| | COMMENTS: |
| | |
| | 1) THERE ARE INDICATIONS OF VINYL, TILE AND CARPET |
| | BEING ADDED INTO THE SPACE. PLEASE SUBMIT THE SPEC |
| | SHEETS FOR THESE MATERIALS ALONG WITH THE FLAME SPREAD |
| | AND SMOKE TESTING FOR THOSE THAT ARE BEING INSTALLED. |
| | |
| | 10.2.7* INTERIOR FLOOR FINISH TESTING AND |
| | CLASSIFICATION. |
| | 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR |
| | FINISHES SHALL |
| | COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR |
| | IGNITION |
| | CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING |
| | MATERIALS. |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN |
| | THE CLASSES SPECIFIED |
| | IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE |
| | CRITICAL RADIANT FLUX |
| | REQUIREMENTS. |
| | 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I |
| | INTERIOR FLOOR FINISH |
| | SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN |
| | 0.45 W/CM2, AS DETERMINED |
| | BY THE TEST DESCRIBED IN 10.2.7.3. |
| | 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II |
| | INTERIOR FLOOR FINISH |
| | SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN |
| | 0.22 W/CM2, BUT LESS |
| | THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN |
| | 10.2.7.3. |
| | |
| | |
| | 2) ANY WORK INVOLVING FIRE SPRINKLERS/FIRE ALARM |
| | SYSTEMS OR EQUIPMENT SHALL BE DONE UNDER SEPARATE |
| | PERMITS AND SHOP DRAWINGS. |
| | |
| | 3) FIRE SPRINKLERS AND FIRE ALARM EQUIPMENT SHALL BE |
| | PROTECTED FROM PAINTING OR DAMAGE. |
| | |
| | 4) THE FIRE SPRINKLER/FIRE ALARM SYSTEMS SHALL BE |
| | MAINTAINED THROUGHOUT DEMO AND RECONSTRUCTION. |
| | |
| | 5) LIFE SAFETY SYSTEMS (FIRE ALARM AND FIRE SPRINKLER) |
| | MUST BE INCLUDED WITH THE MASTER PERMIT IN ACCORDANCE |
| | WITH 61G15-32. |
| | |
| | WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION |
| | CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE. |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | CAITLIN L. FRANCIS |
| | FIRE INVESTIGATOR |
| | 561-804-4728 |
| | [email protected] |
| | |