Plan Review Notes
Plan Review Notes For Permit 22121209
Permit Number 22121209
Review Stop B
Sequence Number 1
Notes
Date Text
2023-01-31 13:40:31WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22121209
 ADD: 4700 N CONGRESS AVE # 201
 CONT: LEIGHTON MCGINN
 TEL: 561-348-4805
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 31ST/ 2023
 ACTION: DENIED
  
 1) SHEET A120 THE EGRESS PLAN DOES NOT SHOW EGRESS TO
 THE REAR STAIRWELL FROM THE MAIN PORTION OF THE TENANT
 SUITE. THERE ARE 2 ISSUES, 1ST MISSING A EXIT
 DIRECTIONAL LIGHT AT DOOR C11 NURSES STATION SIDE OF
 THE DOOR. 2020 FBC-BUILDING CODE SECTION 1013.1. THE
 2ND ISSUE IS WITH DOOR C11 BEING A MANUAL SLIDING
 POCKET DOOR. 2020 FBC-BUILDING CODE SECTION 1010.1.2
 EGRESS DOORS SHALL BE OF THE PIVOTED OR SIDE SWINGING
 TYPE.
  
 2A) SHEET A130 RESTROOMS 218 & 219 BOTH SHOW WALL
 FINISHES P-1 GENERAL WALL PAINT. 2020 FBC-B 1210.2.2.
 WALLS & PARTITIONS. THIS COMMENT IS A RESULT OF THE
 BUILDING OFFICIAL INTERPRETATION ON 06/2020. IN
 BATHROOMS, RESTROOMS & SERVICE SINK AREAS EPOXY PAINT
 IS NO LONGER CONSIDERED A SMOOTH HARD, NON-ABSORBENT
 SURFACE. 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 2B) PLEASE PROVIDE COMPLIANCE WITH THE 2020
 FBC-BUILDING CODE TABLE 2902.1 1 SERVICE SINK IS
 REQUIRED.
  
 3) PLEASE PROVIDE COMPLIANCE WITH THE 2020 FBC-BUILDING
 CODE TABLE 2902.1 DRINKING FOUNTAINS & THE
 FBC-ACCESSIBILITY CODE SECTIONS:
 3A) 2020 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 3B) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT
 MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE
 MORE THAN 4 INCHES HORIZONTALLY INTO THE CIRCULATION
 PATH.
  
 3C) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 3D) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS.
 CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
  
 4) SHEETS A201 DETAIL # 13 & A202 DETAIL # 7 BOTH SHOW
 THE INSTALLATION OF A MICROWAVE, PLEASE PROVIDE
 COMPLIANCE WITH THE 2020 FBC-ACCESSIBILITY CODE
 SECTIONS:
  
 4A) 308 REACH RANGES. 308.2 FORWARD REACH / 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. 308.3 SIDE
 REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 OBSTRUCTED HIGH
 REACH.
  
 4B) 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS
 SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 MAXIMUM.
  
 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER