| Plan Review Notes For Permit 22121142 |
| Permit Number |
22121142 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-04-04 16:35:44 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) NOT RESOLVED. SUBMIT GENERATOR PAD DRAWINGS WITH | | | GENERATOR TO PAD ANCHORING DETAILS. IF A PREFABRICATED | | | GENERATOR PAD WILL BE USED, SUBMIT SIGNED AND SEALED | | | SITE SPECIFIC ENGINEERING FOR IT. FBC AMENDMENTS | | | 107.2.1 | | | | | | 2) NOT RESOLVED. THE GENERATOR IS LOCATED IN A SPECIAL | | | FLOOD HAZARD AREA. THE GENERATOR IS REQUIRED TO BE AT | | | OR ABOVE THE FINISH FLOOR ELEVATION OF THE HABITABLE | | | SPACE OF THE DWELLING OR THE BFE PLUS 2 FEET. THE BFE | | | IS 6 FT NAVD AT THE GENERATOR'S PROPOSED LOCATION. | | | | | | 3) NOT RESOLVED. THE GENERATOR EXHAUST IS REQUIRED TO | | | BE AT LEAST 10 FEET FROM ANY OPENINGS INTO A BUILDING. | | | R303.5.1 INTAKE OPENINGS. | | | MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS | | | SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM | | | ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, | | | CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS | | | AND LOADING DOCKS. | | | | | | 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
|