| 2022-12-30 11:35:02 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION OF PROPSED WOOD FLOOR OVER |
| | EXISTING TILE, BUT NO SPEC SHEET NOR A PRODUCT NAME FOR |
| | THE ACTUAL PROPOSED WOOD FLOORING. |
| | |
| | WOOD FLOORING IS MANUFACTURED AROUND THE WORLD BUT NOT |
| | ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS. |
| | |
| | PER NFPA 101, CH 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | PRODUCT SPEC SHEETS ARE REQUIRED FOR WOOD LVT, AND |
| | WOOD/VINYL LAMINATES. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE WOOD |
| | FLOORING NAME AND THE PRODUCT SPEC SHEETS INDICATING |
| | THE FIRE BEHAVIOR RATING. |
| | |
| | |
| | |
| | 2) THERE IS AN INDICATION OF A NEW SHOWER THAT MAY |
| | INCLUDE DEMO/DAMAGE TO AN EXISTING RATED FIRE WALL. |
| | |
| | ENSURE FIRE RATED TENANT SEPARATION WALLS, IF DAMAGED, |
| | ARE REPAIRED TO THE EXISTING FIRE RATED SEPARATION. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEGMENT ON THE FLOOR |
| | PLAN IN THAT AREA. |
| | |
| | |
| | |
| | 3) IS THE WOOD FLOORING GOING EXTEND ONTO THE BALCONY? |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE INDICATE THE PROPOSED |
| | LOCATIONS OF FLOORING ON THE FLOOR PLAN. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |