| Plan Review Notes For Permit 22121129 |
| Permit Number |
22121129 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-01-13 16:58:54 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II/INSPECTOR | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 1.) FBC B 107.2.1, PLEASE PROVIDE SQUARE FOOT SIZES FOR | | | EACH LETTER FOR EACH TYPE (PYLON, TENANT MONUMENT, AND | | | MONUMENT) OF SIGN. THIS INFORMATION NEEDS TO CORRELATE | | | WITH THE SIGNED/SEALED ENGINEERING SHEET. | | | 2.) FBC B 107.2.1, ALSO PROVIDE, AN UPDATED ENGINEERING | | | SHEET THAT HAS A NEW 3RD PARTY VERIFIABLE | | | SIGNATURE/SEAL AS ENGINEER'S NOTE STATES, " FOR PERMIT | | | USE WITHIN 14 DAYS OF DIGITAL SEAL". | | | 3.) A MAXIMUM HEIGHT AND A MAXIMUM WIDTH OF EACH LETTER | | | OR PROVIDE A NOTE STATING THAT MAXIMUM HEIGHTS AND | | | WIDTHS ARE NOT REQUIRED. |
|