| Plan Review Notes For Permit 22121107 |
| Permit Number |
22121107 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-01-18 13:14:33 | FIRE PROVISO: | | | | | | 1) PER NFPA 101, CH 30 | | | | | | 30.3.3.3 INTERIOR FLOOR FINISH. | | | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN | | | ACCORDANCE WITH | | | SECTION 10.2. | | | | | | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH | | | 10.2.2.2 | | | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL | | | HAVE A | | | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE VINYL | | | FLOORING NAME AND THE PRODUCT SPEC SHEETS INDICATING | | | THE FIRE BEHAVIOR RATING. | | | | | | IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, | | | NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS | | | WOULD NOT BE REQUIRED. | | | | | | PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL | | | FLOORING, WOOD/VINYL LAMINATES, ETC. | | | | | | | | | 2) THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE | | | MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS | | | | | | ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING | | | DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP | | | DRAWINGS. | | | | | | | | | 3) SMOKE ALARMS ARE REQUIRED IN ANY NEW ROOMS/BEDROOMS | | | AS REQUIRED PER NFPA 101 & 72. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|