2023-01-18 13:14:33FIRE PROVISO:
  
 1) PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE VINYL
 FLOORING NAME AND THE PRODUCT SPEC SHEETS INDICATING
 THE FIRE BEHAVIOR RATING.
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS
 WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
 2) THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
  
 3) SMOKE ALARMS ARE REQUIRED IN ANY NEW ROOMS/BEDROOMS
 AS REQUIRED PER NFPA 101 & 72.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709