| 2023-01-31 11:29:57 | ELECTRIC REVIEW FAILED |
| | |
| | 1) PLANS INDICATE ALL INTERIOR PARTITIONS AND CABINETRY |
| | ARE TO BE REMOVED AND REPLACED IN SAME LOCATION. THIS |
| | WILL REQUIRE ALL ELECTRICAL LOCATED IN THESE PARTITIONS |
| | TO BE MODIFIED IN SOME FASHION. PLEASE INDICATE ALL |
| | RECEPTACLES, LIGHT OUTLETS OR OTHER ELECTRIC ITEMS THAT |
| | WILL BE REPLACED, REMOVED OR MODIFIED. DETAIL HOW EACH |
| | DEVICE WILL BE TREATED. FBC 107.2 CONSTRUCTION |
| | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| | THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED |
| | AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL |
| | |
| | 2) PLEASE PROVIDE DETAIL ALL KITCHEN SMALL APPLIANCE |
| | RECEPTACLES AS REQUIRED PER NEC 210.52. A RECEPTACLE |
| | OUTLET SHALL BE INSTALLED AT EACH WALL COUNTERTOP AND |
| | WORK SURFACE THAT IS (12 IN.) OR WIDER. RECEPTACLE |
| | OUTLETS SHALL BE INSTALLED SO THAT NO POINT ALONG THE |
| | WALL LINE IS MORE THAN (24 IN.) MEASURED HORIZONTALLY |
| | FROM A RECEPTACLE OUTLET IN THAT SPACE. PENINSULAR |
| | COUNTERTOP SPACES, AT LEAST ONE RECEPTACLE OUTLET SHALL |
| | BE INSTALLED AT EACH PENINSULAR COUNTERTOP LONG |
| | DIMENSION SPACE WITH A LONG DIMENSION OF (24 IN.) OR |
| | GREATER AND A SHORT DIMENSION OF (12 IN.) OR GREATER. A |
| | PENINSULAR COUNTERTOP IS MEASURED FROM THE CONNECTED |
| | PERPENDICULAR WALL |
| | |
| | 3) PLEASE DETAIL ALL APPLIANCE LOCATIONS, INCLUDE WINE |
| | REFRIGERATOR, WATER HEATER, AC , DOUBLE OVEN, ETC.. FBC |
| | 107.2 |
| | |
| | 4) PLEASE INDICATE BY NOTE ALL NEW WIRING IS TO COMPLY |
| | WITH NEC 210.8 FOR GFCI PROTECTION, NEC 210.12 ARC |
| | FAULT PROTECTION, AND NEC 406.12 FOR TAMPER RESISTANT |
| | RECEPTACLE REQUIREMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |