Plan Review Notes
Plan Review Notes For Permit 22121107
Permit Number 22121107
Review Stop E
Sequence Number 1
Notes
Date Text
2023-01-31 11:29:57ELECTRIC REVIEW FAILED
  
 1) PLANS INDICATE ALL INTERIOR PARTITIONS AND CABINETRY
 ARE TO BE REMOVED AND REPLACED IN SAME LOCATION. THIS
 WILL REQUIRE ALL ELECTRICAL LOCATED IN THESE PARTITIONS
 TO BE MODIFIED IN SOME FASHION. PLEASE INDICATE ALL
 RECEPTACLES, LIGHT OUTLETS OR OTHER ELECTRIC ITEMS THAT
 WILL BE REPLACED, REMOVED OR MODIFIED. DETAIL HOW EACH
 DEVICE WILL BE TREATED. FBC 107.2 CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL
  
 2) PLEASE PROVIDE DETAIL ALL KITCHEN SMALL APPLIANCE
 RECEPTACLES AS REQUIRED PER NEC 210.52. A RECEPTACLE
 OUTLET SHALL BE INSTALLED AT EACH WALL COUNTERTOP AND
 WORK SURFACE THAT IS (12 IN.) OR WIDER. RECEPTACLE
 OUTLETS SHALL BE INSTALLED SO THAT NO POINT ALONG THE
 WALL LINE IS MORE THAN (24 IN.) MEASURED HORIZONTALLY
 FROM A RECEPTACLE OUTLET IN THAT SPACE. PENINSULAR
 COUNTERTOP SPACES, AT LEAST ONE RECEPTACLE OUTLET SHALL
 BE INSTALLED AT EACH PENINSULAR COUNTERTOP LONG
 DIMENSION SPACE WITH A LONG DIMENSION OF (24 IN.) OR
 GREATER AND A SHORT DIMENSION OF (12 IN.) OR GREATER. A
 PENINSULAR COUNTERTOP IS MEASURED FROM THE CONNECTED
 PERPENDICULAR WALL
  
 3) PLEASE DETAIL ALL APPLIANCE LOCATIONS, INCLUDE WINE
 REFRIGERATOR, WATER HEATER, AC , DOUBLE OVEN, ETC.. FBC
 107.2
  
 4) PLEASE INDICATE BY NOTE ALL NEW WIRING IS TO COMPLY
 WITH NEC 210.8 FOR GFCI PROTECTION, NEC 210.12 ARC
 FAULT PROTECTION, AND NEC 406.12 FOR TAMPER RESISTANT
 RECEPTACLE REQUIREMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  