| Plan Review Notes For Permit 22121068 |
| Permit Number |
22121068 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2023-01-27 10:44:11 | 3RD REVIEW FMC | | | PERMIT: 22121068 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) WSHP2-3: 1021 SQ.FT. CONFERENCE ROOM REQUIRES 321 | | | CFM???S OF OUTDOOR AIR. WSHP 2-5: 911 SQ. FT. | | | CONFERENCE ROOM REQUIRES 285 CFM???S OF OUTDOOR AIR. | | | WSHP 2-10: 270 SQ. FT. RECEPTION AREA REQUIRES 61 | | | CFM???S OF OUTDOOR AIR. WSHP 2-11: 460 SQ. FT. | | | CONFERENCE ROOM REQUIRES 143 CFM???S OF OUTDOOR AIR. | | | PLEASE MAKE THESE CORRECTIONS ON SHEETS M2.1 AND M2.3. | | | FMC 403.3.1.1 AND TABLE 403.3.1.1. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|