| 2022-12-30 07:45:22 | 1ST GAS REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2020 FRC G2412.2 (401.2)/2018 NFPA 6.4.1.1 - AN |
| | UNDERGROUND TANK SHALL BE 10 FEET FROM AN ADJOINING |
| | PROPERTY LINE THAT CAN BE BUILT UPON IN ACCORDANCE WITH |
| | TABLE 6.4.1.1, TABLE 6.5.1.2, 6.4.1.2 THROUGH 6.4.1.3, |
| | 6.4.3, 6.4.4.1 THROUGH 6.4.4.4, AND 6.5.3.6 THROUGH |
| | 6.5.3.11. |
| | |
| | 2. 2020 FRC G2427.8 #2 - PLEASE SHOW THE LOCATION OF |
| | THE OPENINGS INTO THE STRUCTURE TO SHOW COMPLIANCE WITH |
| | THIS SECTION. 4 FEET FROM ANY DOOR, OPERABLE WINDOW, OR |
| | GRAVITY AIR INLET. |
| | |
| | 3. 2017 WPB AMENDS 107.2.1 - PLEASE HAVE THE PERSON WHO |
| | DESIGNED THE DRAWING PRINT THEIR NAME, SIGN THEIR NAME, |
| | AS WELL AS PUT THE CONTRACTOR'S NUMBER ON THE DRAWING |
| | AS REQUIRED BY THE WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1. |
| | |
| | |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |