| Plan Review Notes For Permit 22121061 |
| Permit Number |
22121061 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-01-30 15:17:06 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. PROVIDE INFORMATION OF THE FOLLOWING FEEDERS | | | (INCLUDING PROTECTION AND EQUIPMENT GROUNDING | | | CONDUCTORS IN ACCORDANCE WITH NEC 215, 250.122 : | | | A. EX. METER TO EX PANEL "6H" 200A | | | B. EX PANEL '6H1" 200A TO EX PANEL "6H2" | | | | | | 2. PROVIDE INFORMATION OF THE 75 KVA TRANSFORMER | | | PRIMARY AND SECONDARY CONDUCTORS AND PROTECTION. NEC | | | 450 | | | | | | 3. PROVIDE INFORMATION OF SERVICE CONDUCTORS. NEC 230 | | | | | | END OF COMMENTS | | | |
|