| Date |
Text |
| 2023-03-13 16:30:03 | 2ND PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. DONE |
| | |
| | 2. THIS COMMENT NOT ADDRESSED. THIS COMMENT IS FOR HOT |
| | WATER DELIVERY. YOUR RESPONSE ADDRESSES TEMPERED WATER. |
| | THE WATER HEATER DETAIL SHOULD SHOW A MIXING VALVE. |
| | PER FBC 607.1.1, 613.1, PROVIDE A TEMPERATURE-ACTUATED |
| | MIXING VALVE, INSTALLED TO REDUCE WATER TEMPERATURES TO |
| | DEFINED LIMITS, SHALL COMPLY WITH ASSE 1017. SUCH VALVE |
| | SHALL BE INSTALLED AT THE HOT WATER SOURCE. THIS |
| | PROTECTION LEVEL IS IN ADDITION TO THE REQUIREMENTS |
| | NEEDED FOR PUBLIC HAND WASHING DICTATED BY FBC PL |
| | 419.5, 607.1.2. |
| | |
| | 3. DONE |
| | |
| | 4. DONE |
| | |
| | 5. 2020 FPC 905.4 - THE VENTS FOR THE SHOWERS ARE NOT |
| | ALLOWED TO BE HORIZONTAL WHILE DRY. EACH VENT MUST |
| | REMAIN VERTICAL UNTIL 6" ABOVE THE FIXTURE(S) SERVED. |
| | |
| | 6. 2020 FPC 918.8 - AN AIR ADMITTANCE VALVE CANNOT BE |
| | USED TO VENT THE GREASE TRAP. THIS CREATES AN "AIR |
| | BOUND" TRAP. A VENT TO THE OPEN AIR IS REQUIRED. |
| | |
| | 7. 2017 WPB AMEND - 105.1/107.3 -- THE BACKFLOW DEVICE |
| | AT THE UTILITY CONNECTION AND THE GREASE TRAP REQUIRE |
| | SEPARATE PERMITS THAT ARE REQUIRED TO BE APPLIED FOR |
| | PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS |
| | APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE |
| | DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY |
| | EMAILING A COMPLETED PERMIT APPLICATION TO |
| | [email protected]. AFTER YOU HAVE THE PERMIT(S) |
| | GENERATED, NOTIFY ME VIA EMAIL OR NOTE IN THE RESPONSE |
| | LETTER AND I WILL COMPLY THIS COMMENT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | |
| | |
| | |
| | |
| | |