| 2023-01-09 16:24:21 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22121052 2025 N DIXIE HWY |
| | |
| | 1ST REVIEW |
| | |
| | A SEPARATE PERMIT FOR GREASE INTERCEPTOR IS REQUIRED TO |
| | BE SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY PERMIT |
| | (AS APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" |
| | (TO BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR |
| | SELECTED BY EMAILING A COMPLETED PERMIT APPLICATION TO |
| | [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. A SEPARATE PERMIT IS |
| | REQUIRED HOWEVER A REVIEW OF THE SYSTEM UNDER THE MAIN |
| | PERMIT IS ALSO REQUIRED. |
| | AFTER YOU HAVE THE PERMIT(S) GENERATED, PLEASE NOTIFY |
| | ME AT [email protected] AND CC SAMANTHA HILL, CHIEF PLANS |
| | EXAMINER AT [email protected] AND RYAN BROWN, CHIEF |
| | PLUMBING INSPECTOR AT [email protected] VIA EMAIL WITH |
| | THE PERMIT NUMBER(S). |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS (SEE FBC PL 404.1) BUT IS TYPICALLY ADDRESSED |
| | ON THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING |
| | THESE REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED |
| | PRIOR TO A PLUMBING REVIEW APPROVAL. |
| | ***A) PLAN G1.2: PROVIDE ADDITIONAL DETAILS (PLAN AND |
| | ELEVATION) FOR STANDARD ROLL IN SHOWER WITH SEAT |
| | SHOWING DIMENSIONS, LOCATIONS AND HEIGHTS OF GRAB BARS, |
| | CONTROL VALVE, FAUCETS, SHOWER SPRAY UNIT. COMPLY WITH |
| | FBC ACC 608.2.2, 608.3.2, 608.5.2, 608.6, 609.4, 610.3, |
| | 610.3.1. |
| | ***B) PROVIDE DETAIL FOR ACCESSIBLE WASHER AND DRYER |
| | SHOWING COMPLIANCE WITH FBC ACC 611.3 |
| | ***C) PROVIDE CLEAR FLOOR SPACE FOR ACCESSIBLE WASHER |
| | AND DRYER SHOWING COMPLIANCE WITH FBC ACC 611.2, 305. |
| | |
| | 2. PER FBC 607.1.1, 613.1, PROVIDE A |
| | TEMPERATURE-ACTUATED MIXING VALVE, INSTALLED TO REDUCE |
| | WATER TEMPERATURES TO DEFINED LIMITS, SHALL COMPLY WITH |
| | ASSE 1017. SUCH VALVE SHALL BE INSTALLED AT THE HOT |
| | WATER SOURCE. THIS PROTECTION LEVEL IS IN ADDITION TO |
| | THE REQUIREMENTS NEEDED FOR PUBLIC HAND WASHING |
| | DICTATED BY FBC PL 419.5, 607.1.2. |
| | |
| | 3. IT APPEARS THE HOT WATER PIPING FROM THE HOT WATER |
| | SOURCE TO THE PUBLIC LAVATORIES EXCEEDS 2 FEET. REFER |
| | TO TABLE C404.5.1 FBC EC- THE 1/2 -INCH HOT WATER PIPE |
| | TO THE LAVATORY SHALL NOT EXCEED 2 FEET FROM THE HOT |
| | WATER SOURCE. |
| | |
| | 4. RE: P-2.1, P-5.1; CIRCUIT VENTED BRANCH FOR WATER |
| | CLOSETS |
| | ***A) THE CIRCUIT VENT CONNECTION SHALL BE LOCATED |
| | BETWEEN THE TWO MOST UPSTREAM FIXTURE DRAINS (WATER |
| | CLOSETS). FBC PL 914.2 |
| | ***B) FIXTURES OTHER THAN THE CIRCUIT VENTED FIXTURES |
| | DISCHARGING TO THE CIRCUIT VENTED BRANCH SHALL BE |
| | INDIVIDUALLY OR COMMON VENTED. FBC PL 914.5 |
| | |
| | 5. RE: P-2.1, P-5.1; SHOWER DRAINS |
| | ***A) BRANCH SHALL BE SIZED 3 INCH TO THE CONNECTION |
| | WITH MOST UPSTREAM SHOWER FIXTURE DRAIN. FBC PL TABLE |
| | 915.2.2 |
| | ***B) VENT SHALL CONNECT ABOVE THE CENTERLINE OF THE |
| | DRAIN OF THE HORIZONTAL DRAIN AND SHALL RISE VERTICALLY |
| | TO A POINT NOT LESS THAN 6 INCHES ABOVE THE FLOOD LEVEL |
| | RIM OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED |
| | PER FBC PL 905.3 AND 905.4. O BE CLEAR, THERE SHALL BE |
| | NO HORIZONTAL TRAVEL BETWEEN THE BRANCH AND THE |
| | VERTICAL PORTION OF THE VENT. |
| | ***C) PER FBC PL 915.2.5, SHOWER FIXTURE DRAINS SHALL |
| | NOT EXCEED THE MAXIMUM ALLOWABLE DISTANCE FROM TRAP TO |
| | VENT AS ALLOWED IN FBC PL TABLE 909.1 UNLESS SIZED THE |
| | SAME AS THE BRANCH. |
| | |
| | 6. TRAPPED FLOOR SINK DISCHARGING TO GREASE INTERCEPTOR |
| | SHALL BE VENTED. FBC PL 909.1 |
| | PLEASE NOTE, A SEPARATE PERMIT FOR THE GREASE |
| | INTERCEPTOR IS REQUIRED. |
| | |
| | 7. PLEASE PROVIDE SIZES AND MINIMUM SLOPES OF PRIMARY |
| | AND SECONDARY STORM DRAINS. FBC PL 1106.2, TABLE 1106.2 |
| | |
| | 8. PLEASE PROVIDE OVERFLOW SCUPPERS FOR PADEL COURT |
| | ROOF. FBC PL 1108.1 |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |