| 2023-02-08 12:41:34 | 3RD GAS REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. DONE |
| | |
| | 2. DONE |
| | |
| | 3. THE EXISTANCE OF A HOOD DOES NOT SUPPLY COMBUSTION |
| | AIR - YOU NEED TO SHOW THAT THE CALCULATIONS OF THE |
| | CUBIC FEET OF THE SPACE USED AND THAT THERE IS AT LEAST |
| | 50 CUBIC FEET PER 1000 BTU, OR SUPPLY COMBSTION AIR BY |
| | ONE OF THE APPROVED METHODS. YOU SHOULD BE SHOWING ME |
| | THE CUBIC FOOT IN A COMMUNICATED SPACE WITHOUT BARRIERS |
| | OR DOORS AND DIVIDE BY THE NUMBER OF BTU'S USED. SEE |
| | SECTION 304.1 FOR MORE INFORMATION. |
| | |
| | COMBUSTION AIR CALCULATIONS ARE REQUIRED - SHOW THE |
| | 715,000 BTU HAS ENOUGH AIR WITHIN THE SPACE USED. |
| | - 2020 FGC 304.1 - - PROVIDE MEASUREMENTS AND |
| | CALCULATIONS FOR THE COMBUSTION AIR, OR SHOW THAT IT IS |
| | NOT NEEDED. |
| | |
| | 4. DONE |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |