| 2022-12-30 07:20:43 | 1ST PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMENDS 107.3.5.1.5 - PLEASE SUBMIT A |
| | DRAWING THAT INCLUDES THE EXISTING SYSTEM FOR SIZING |
| | CONFIRMATION. THE EXISTING SYSTEM MUST BE VERIFIED TO |
| | BE SIZED CORRECTLY IN ORDER TO SUPPLY THE NEW BRANCH. |
| | THIS SHOULD BE CONSIDERED FOR EVERY ADDITION TO A GAS |
| | SYSTEM. YOUR SIZING TABLE SHOULD BE FOR THE "LONGEST |
| | RUN" IN THE WHOLE SYSTEM, NOT THE DEVELOPED LENGTH OF |
| | THE ADDITION. |
| | |
| | 2. 2017 WPB AMENDS 107.3.5.1.5 - PROVIDE DETAILS OR |
| | NOTATION OF EXISTING VENTING FOR THE APPLIANCES. IS |
| | THIS UNDER AN EXISTING HOOD? |
| | |
| | 3. 2017 WPB AMENDS 107.3.5.1.5 - PROVIDE MEASUREMENTS |
| | AND CALCULATIONS FOR THE COMBUSTION AIR, OR SHOW THAT |
| | IT IS NOT NEEDED. |
| | |
| | 4. 2017 WPB AMENDS 107.3.5.1.5 - LABEL THE TYPE OF GAS. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |